Adjustable Voltage, Frequency And Reconnection Settings - Xantrex GT5.0-NA-240 Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

Specifications

Adjustable Voltage, Frequency and Reconnection Settings

Utility disconnect settings can be adjusted using the GTConfigLite software tool.
Permission of the utility must be granted before adjusting any of these settings.
For more information about installing and using GTConfigLite, see the GTConfigLite
User's Guide (p/n 976-0260-01-01), available with the software.
Setting
Phase-to-Neutral (rms) High Threshold
Voltage
Phase-to-Neutral (rms) Reconnect
Voltage
Phase-to-Neutral (rms) Low Threshold
Voltage
Voltage (rms) High Clearing Time (ms) 1000
Voltage (rms) Low Clearing Time (ms) 2000
Frequency High Threshold
Frequency Low Threshold
Frequency High Clearing Time (ms)
Frequency Low Clearing Time (ms)
Reconnect Delay (ms)
A–10
Default Tolerance
131.50
+0.5, –2.5 V 130.50 135.00
126.96
±0.24 V
106.10
–0.5, +2.5 V 102.00 107.10
+0, –0.1 s
60.40
±0.1 Hz
59.40
160
+0, –0.1 s
160
305000
n/a
Adjustment Range
Low
High
Tolerance
±1.5 V
126.96 135.00
±1.5 V
±1.5 V
1000
2000
+0, –0.1 s
2000
5000
60.40
60.60
±0.1 Hz
57.00
59.80
160
200
+0, –0.1 s
160
300000
60000
305000 n/a
975-0334-01-01