Gt4.0 - Xantrex GT5.0-NA-240 Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

Specifications

GT4.0

Input
Model number
Input voltage, Maximum
Power Point range
Absolute maximum array
open circuit voltage
Maximum input current
Maximum array short
circuit current
Reverse polarity
protection
Ground fault protection
Output
Nominal output voltage
Maximum output power
Operating range, utility voltage (phase to phase)*
Operating range, utility voltage (phase to neutral)*
Nominal output frequency
Operating range, utility frequency*
Startup current
Maximum continuous output current
Maximum output fault current
Maximum output overcurrent protection
Maximum utility backfeed current
Total Harmonic Distortion
Power factor
Utility monitoring— islanding protection
Output characteristics
Output current waveform
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable trip limits
and may be aggregated above 30 kW on a single Point of Common Coupling. See "Adjustable Voltage, Frequency
and Reconnection Settings" on page A–10.
A–4
GT4.0N-NA-240/208 UL-05
864-1008
Certified operating range:
240–480 Vdc. (Unit is operable
as low as 235 Vdc and as high as
550 Vdc.)
18 Adc (240 V), 17 Adc (208 V)
GT4.0-NA-240/208 UL-05 GT4.0-NA-240/208-POS UL-05
864-1007
Certified operating range:
195–550 Vdc. (Unit is
operable as low as 193 Vdc.)
600 Vdc
22 Adc (240 V), 21 Adc (208 V)
24 Adc
Short circuit diode
GF detection, I
DIF
240 V
4000 W
212–263 Vac
106.1–131.5 Vac
59.3–60.5 Hz
16.7 A
25 A RMS
>0.99% (at rated power), >0.95% (full power range)
Vac, fac as per UL 1741 (2005)
Current source
864-1010
Certified operating range:
195–550 Vdc. (Unit is operable
as low as 193 Vdc.)
> 1 A
208 V
3800 W
184–228 Vac
60 Hz
0 Aac
18.3 A
25 A
0 A
<5%
Sine wave
975-0334-01-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents