Adjustable Disconnect Settings

Setting
AC Low Voltage
AC High Voltage
AC Low Frequency
AC High Frequency
Reconnect Delay
Output Power Versus Ambient Temperature
975-0131-01-01
The adjustable disconnect setting values vary depending on whether the inverter is
a 208 Vac/60 Hz, 240 Vac/60 Hz, or 230 Vac/50 Hz model. Utility permission is
required prior to changing the settings on the inverter.
The default values of these settings differ from the utility specifications on
page A–2. These differences take into account the accuracy ranges listed in the
table below, and are intended to ensure that utility specifications are always met.
Default Values
208 Vac/60 Hz 240 Vac/60 Hz 230 Vac/50 Hz
186 Vac
214 Vac
225 Vac
261 Vac
59.4 Hz
60.4 Hz
305 sec.
Once the heat sink on the inverter reaches a maximum temperature limit, the GT
Inverter reduces its energy output to ensure maximum component ratings are not
exceeded.
3500
3000
2500
2000
1500
1000
500
0
-25
-15

Figure A-1 Output Power vs. Ambient Temperature

205 Vac
250 Vac
47.1 Hz
50.9 Hz
GT3.0 GRID TIE SOLAR INVERTER
Output Power versus Ambient Temperature
-5
5
15
25
Ambient Temperature (C)
Standard Unit
Electrical Specifications
Adjustment Range
From...
To...
180 Vac
269 Vac
46.0 Hz
62.0 Hz
60 sec.
600 sec.
35
45
55
w/ Optional Fan Kit
Accuracy
+/– 3 Vac
+/– 0.1 Hz
+/– 5 sec.
65
A–3