Gt3.3 - Xantrex GT5.0-NA-240 Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

Specifications

GT3.3

Input
Model number
Input voltage, Maximum
Power Point range
Absolute maximum array
open circuit voltage
Maximum input current
Maximum array short circuit
current
Reverse polarity protection
Ground fault protection
Output
Nominal output voltage
Maximum output power
Operating range, utility voltage (phase to phase)*
Operating range, utility voltage (phase to neutral)
Nominal output frequency
Operating range, utility frequency*
Startup current
Maximum continuous output current
Maximum output fault current
Maximum output overcurrent protection
Maximum utility backfeed current
Total Harmonic Distortion
Power factor
Utility monitoring— islanding protection
Output characteristics
Output current waveform
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable
trip limits and may be aggregated above 30 kW on a single Point of Common Coupling. See "Ad-
justable Voltage, Frequency and Reconnection Settings" on page A–10.
A–6
GT3.3N-NA-240/208 UL-05
864-1006
Certified operating range:
200–400 Vdc. (Unit is operable
as high as 550 Vdc.)
17.5 Adc (240 V),
16.5 Adc (208 V)
240 V
3300 W
212–263 Vac
*
13.8 A
>0.99% (at rated power), >0.95% (full power range)
GT3.3-NA-240/208 UL-05 GT3.3-NA-240/208-POS UL-05
864-1004
Certified operating range: 195–550 Vdc.
(Unit is operable as low as 193 Vdc.)
600 Vdc
18 Adc (240 V), 17 Adc (208 V)
24 Adc
Short circuit diode
GF detection, I
> 1 A
DIF
208 V
3100 W
184–228 Vac
106.1–131.5 Vac
60 Hz
59.3–60.5 Hz
0 Aac
14.9 A
20 A
20 A RMS
0 A
<5%
Vac, fac as per UL 1741 (2005)
Current source
Sine wave
864-1005
975-0334-01-01