Electrical Specifications; Gt5.0 - Xantrex GT5.0-NA-240 Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

Specifications

Electrical Specifications

GT5.0

Input
Model number
Input voltage, Maximum Power Point range
Absolute maximum array open circuit voltage
Maximum input current
Maximum array short circuit current
Reverse polarity protection
Ground fault protection
Output
Nominal output voltage
Maximum output power
Operating range, utility voltage (phase to phase)*
Operating range, utility voltage (phase to neutral)
Nominal output frequency
Operating range, utility frequency*
Startup current
Maximum continuous output current
Maximum output fault current
Maximum output overcurrent protection
Maximum utility backfeed current
Total Harmonic Distortion
Power factor
Utility monitoring— islanding protection
Output characteristics
Output current waveform
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable trip limits
and may be aggregated above 30 kW on a single Point of Common Coupling. See "Adjustable Voltage, Fre-
quency and Reconnection Settings" on page A–10.
A–2
GT5.0-NA-240/208 UL-05
864-1009
Certified operating range: 240–550 Vdc.
(Unit is operable as low as 235 Vdc.)
22.0 Adc (240 V), 20.0 Adc (208 V)
240 V
5000 W
212–263 Vac
*
21 A
>0.99% (at rated power), >0.95% (full power range)
Vac, fac as per UL 1741 (2005)
GT5.0-NA-240/208-POS UL-05
864-1011
600 Vdc
24 Adc
Short circuit diode
GF detection, I
> 1 A
DIF
208 V
4500 W
184–228 Vac
106.1–131.5 Vac
60 Hz
59.3–60.5 Hz
0 Aac
22 A
30 A
30 A RMS
0 A
<3%
Current source
Sine wave
975-0334-01-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents