Shifting Input Values

4-1

Shifting Input Values

4-1-1

Shifting Inputs

One-point shift
Operation Procedure
Operation level
C
30
200
1,2,3...
Adjustment level
at
off
Temperature
C
in5
input shift
0.0
C
in5
1.0
Operation level
C
31
20.0
52
• The input shift type matched to the sensor currently selected in the "input
type" parameter is displayed.
• Two-point shift is applied only for infrared temperature sensors.
• With one-point shift, only the value set to the "Temperature input shift"
parameter (adjustment level) is applied to the entire temperature input
range. For example, if the input shift value is set to "1.2 ° C", the process
value is treated as "201.2 ° C" after input shift is applied when the process
value is 200 ° C.
Temperature
Upper-limit
value
Lower-limit
value
0
In this example, let's shift the input of the K sensor by "1 ° C" by one-point input
shift.
Operation level
1. Press the
key to move from the "operation level" to the "adjustment
level".
2. Select the "temperature input shift" parameter by pressing the
3. Press the
or
4. To return to the "operation level," press the
1 ° C larger than before shift is applied.
After shift
Before
shift
Input shift value
100
key to set "1.0".
Section 4-1
Input
key.
key. The process value is