Horizontal / Vertical Combination Venting - kozy heat Thief River Falls-TRF 56701 Installation And Operation Manual

Direct vent fireplace
Hide thumbs Also See for Thief River Falls-TRF 56701:
Table of Contents

Advertisement

NOTE: Page 26 has infor-
mation on restrictor instal-
lation in conjunction with
venting installation.
Page 51 has information on restrictor
recommendations depending on burner
flame appearance and instructions on
installation after venting is completed.
Horizontal sections require 1/4" (6 mm)
rise for every 12" (305 mm) of travel.
Flange on top stand-off must be bend
upwards to a 90˚ angle when top venting.
For each additional elbow used after the first
elbow, 3 ft. (914 mm) must be subtracted
from the maximum venting allowed. For
each 45° elbow used, 1-1/2 ft. (457 mm)
must be subtracted from the maximum vent-
ing allowed.
(2) 45° degree elbows may be used in place
of (1) 90° elbow.
CAUTION: This gas appliance
must not be connected to or
joined with any other chimney
flue serving another appliance.
IMPORTANT: A WALL THIMBLE PASS-THRU MUST BE USED ON ALL HORIZONTAL VENT RUNS THAT PASS
THROUGH EITHER INTERIOR OR EXTERIOR WALLS. FOLLOW VENT SYSTEM MANUFACTURER‟S INSTRUCTIONS.
VENTING
PAGE 27
(Horizontal & Vertical Combination)
TERMINATION MUST BE
WITHIN SHADED AREA.
HORIZONTAL / VERTICAL
COMBINATION
20‟ (6.10 m) VERTICAL
10‟ (3.05 m) HORIZONTAL