Processor Reset; Usb Port Not Connected; Data Fault During Configuration Upload - Bosch Plena Voice Alarm System Installation And Operation Manual

Hide thumbs Also See for Plena Voice Alarm System:
Table of Contents

Advertisement

Plena Voice Alarm System
Figure 8.2 Silent message action programming
When the alarm is stopped with the Trigger Input Stop all zones will be silent but the system
will still be in Emergency State. The end user then needs to press Emergency Acknowledge
and Emergency Reset to terminate this Emergency State.
8.11

Processor Reset

This fault can occur when the Service DIP Switches are left in the wrong position. This
frequently occurs when people have downloaded new firmware. The correct positions should
be SEL0 and SEL1 to on, and Enable Firmware Download to off.
The fault indication for Processor Reset cannot be disabled, neither in the configuration nor
with the dipswitch Supervision at the back of the Controller.
8.12

USB port not connected

This error message can occur when the Configuration Software is just installed. Although
there is no such instruction displayed during installation it is recommended that your PC is
rebooted after installing the Configuration Software.
This problem could also occur when the Service DIP Switches are in the wrong position. A
more common problem in such a case is a Processor Reset Fault. However if fault supervision
is disabled this fault indication will not occur and USB port not connected could occur. Please
refer to the section Processor Reset for more information.
8.13

Data fault during configuration upload

This fault occurs when the Configuration Software you are using and the Firmware on the
Controller to which you are uploading have a different incompatible version.
Bosch Security Systems B.V.
Installation and Operation manual
Troubleshooting | en
9922 141 1037x (V2.16) | V0.6 | 2011.09
89