Plena Voice Alarm System
Clause / Requirement
b
c
d
e
Bosch Security Systems B.V.
1
the optional functions with requirements
of this European Standard,
2
the functions relating to other parts of
EN 54, and
3
the ancillary functions not required by
this European Standard;
technical specifications of the inputs and
outputs of the VACIE, sufficient to permit an
assessment of the mechanical, electrical, and
software compatibility with other
components of the system (e.g. as described
in EN 54-1), including where relevant
1
the power requirements for
recommended operation,
2
the maximum number of voice alarm
zones,
3
information concerning the connection of
emergency microphones,
4
the maximum and minimum electrical
ratings for each input and output,
5
information on the communication
parameters employed on each
transmission path,
6
recommended cable parameters for each
transmission path, and
7
fuse ratings;
specified means to limit the consequences of
fault (see 13.5.2);
configuring and commissioning instructions;
operating instructions;
Installation and Operation manual
Compliance
The inputs and outputs for audio and
control are described in the IUI, including
the technical data, system functions,
configuration instructions, compliancy to
standards. This includes the information
as requested in 13.2.1 b) 1)..7).
The Open Interface is described in the
'Software manual of the voice alarm
system.
Power requirements are described in the
respective manuals.
This is described in the respective
manuals.
This is described in the respective
manuals.
This is described in the respective
manuals.
This is described in the respective
manuals.
This is described in the respective
manuals.
Main fuse ratings are described.
The IUI describes the following means to
limit the consequences of fault:
Switchover to spare (standby)
amplifiers
Audio/control input supervision
Backup power supply
Loudspeaker line supervision
The ability of the emergency
microphone to make a 'fail safe' call
in case of a controller defect
A/B group wiring of loudspeakers
Configuring and commissioning
instructions are included in the IUI/SCM
(installation and user instruction and
software configuration manual).
Operating instructions are included in
the IUI.
9922 141 1037x (V2.16) | V0.6 | 2011.09
| en 141