Advertisement

Plena Voice Alarm System
Mic/line input with VOX functionality
Type:
Sensitivity:
Impedance:
VOX threshold:
BGM
Type:
Nominal input level:
Line out
Type:
Nominal output level:
Maximum output level:
External power amplifier
Type:
Controller output/Amplifier input:
Controller input/Amplifier output:
10.1.2

Voice Alarm Router

Electrical
Mains voltage:
Mains current:
Max. mains inrush current:
Battery voltage:
Battery current:
NOTICE!
Maximum load means maximum power out, maximum load 24 V(DC) out and maximum
number of call stations.
Interconnection
Voice Alarm Router :
External power amplifiers:
Bosch Security Systems B.V.
Installation and Operation manual
3-pin XLR, 6.3 mm jack socket, balanced
1 mV +1/-3 dB (mic), 1 V +1/-3 dB (line)
> 10 kΩ
500 µV (mic), 500 mV (line)
Cinch, stereo converted to mono
500 mV
3-pin XLR, 6.3 mm jack socket, balanced
1 V
1 V
3-pin XLR and screw terminals
1 V
100 V
230/115 V(AC), ± 10%, 50/60 Hz
0.2 A (system idle)
0.3 A (maximum load)
1.5 A (for mains voltage of 220 - 240 V)
3 A (for mains voltage of 100 - 120 V)
20.0 to 26.5 V(DC)
0.5 A (system idle)
1.5 A (maximum load)
RJ45 socket, CAN bus; max. 2 routers
3-pin XLR and screw terminals, max. 5 A;
max. rated output 1000 W
9922 141 1037x (V2.16) | V0.6 | 2011.09