Clause / Requirement
12.2.1 Where more than one emergency
microphone can be connected to the VACIE,
the emergency microphones shall be
configurable for priority at access level 3 or
access level 4.
12.2.2 Where more than one emergency
microphone is configured at each priority
level, only one microphone shall be active at
any one time.
Bosch Security Systems B.V.
Compliance
Configuration of the emergency
microphones is performed via the PC
interface of the controller. This PC
program requires access level 3.
For emergency microphones 3 priority
levels are available, for each possible
MEG microphone location. Maximum
three EMG microphone is a system:
controller and maximum two remote
control panels.
Microphones should be configured for
different priorities.
Installation and Operation manual
Signature
9922 141 1037x (V2.16) | V0.6 | 2011.09
| en 139