2-Channel Mode Operation; Supervision - Bosch Plena Voice Alarm System Installation And Operation Manual

Hide thumbs Also See for Plena Voice Alarm System:
Table of Contents

Advertisement

Plena Voice Alarm System
6.1.5

2-Channel mode operation

If the 2ch operation switch (see Figure 6.1) is in the ON position, the system operates in the 2-
channel mode.
Voice alarm controller
In the 2-channel mode, the BGM is amplified by the internal power amplifier of the voice alarm
controller. The calls are amplified by the external power amplifier, which is connected to the
voice alarm controller (see section 5.1.4 ). If the external power amplifier is faulty, the calls
are amplified by the internal power amplifier. In 2-channel mode, calls do not interrupt the
BGM.
Amplifier
Internal
External
Table 6.4 2-channel mode, controller
Voice alarm router
One or two external power amplifiers can be connected to a voice alarm router to increase the
power of the system (see section 5.2.5 ). In 2-channel mode:
Amplifier
1
2
Table 6.5 2-channel mode, router
6.2

Supervision

If the Supervision switch (see Figure 6.1) is in the ON position, supervision is enabled. If it is
in the OFF position, supervision is disabled.
NOTICE!
Supervision is only necessary for systems that have to comply to the IEC60849 evacuation
standard. If the system does not have to comply to this standard, leave the switch in the OFF
position.
If the Supervision switch is in the OFF position, the Disabled indicator on the front panel of
the voice alarm controller is lit (see Figure 6.2) to indicate that supervision is switched off.
Figure 6.2 Disabled indicator
Bosch Security Systems B.V.
External power amplifier 1 of the voice alarm router is used to increase the power of the
internal power amplifier of the voice alarm controller.
External power amplifier 2 of the voice alarm router is used to help the external power
amplifier of the voice alarm controller to amplify calls.
Fault Indicators
0 dB
-6dB
-20dB
Installation and Operation manual
Function
BGM/Spare power amplifier.
Call power amplifier.
Function
BGM/Spare power amplifier.
Call power amplifier.
Processor reset
Mains
Battery
Network
Message
Call/EMG
Music/Spare
EMG mic
Ground short
RCP
Input
Router
Configuration | en
Disabled
A
B
Zone1
Zone2
Zone3
Zone4
Zone5
Zone6
9922 141 1037x (V2.16) | V0.6 | 2011.09