Clause / Requirement
A stiff-covered maintenance manual should be
available giving details of all work required to
maintain the installation and equipment in proper
working order, consistent with specified
performance criteria and any other requirements of
this standard and other relevant international or
national standards. This should state clearly:
a
b
c
d
e
f
g
h
A.1.3

EN60849 - When using the Plena Remote Control Kits:

The Plena Remote Control Kit and the Plena Remote Control Extension Kit are versions of the
Remote Control and Remote Control Extension with connector interfaces instead of LED and
buttons. These kits enable the use to built custom panels for the Voice alarm System.
Functionality and firmware is identical to the remote control (extension). The compliancy to
IEC60849 is valid as long as the buttons and LED's/lamps are connected correctly. This should
be done by a qualified electrician. Furthermore the final installation should always be tested
according to the above standard to ensure proper functioning.
When installing in a 19" rack please ensure the following:
A.1.4

EN54-16 (valid for version 2.16.xx)

EN 54-16 is a product standard governing 'Voice Alarm Control and Indicating Equipment'
(VACIE) which is issued by the European Union Construction Product Directive (CPD), also
Bosch Security Systems B.V.
The method of maintenance.
Any sequence related to maintenance.
Identification of parts requiring maintenance,
giving reference to the location of items on
drawings, together with manufacturer's
reference numbers, and the addresses,
telephone and facsimile numbers, of suppliers
of materials and parts.
Original versions of equipment and materials
catalogues.
List and location of spare parts.
List and location of special tools.
The maintenance instructions should also
include:
Test certificates as required to be examined by
the relevant authority.
A set of "as fitted" drawings.
Ventilation requirements are met and ambient temperature inside rack is below 55
degrees.
Indications are visible from the outside.
The sounder is audible.
Access level control is met if applicable.
The rack is properly grounded.
Installation and Operation manual
Compliance
Responsibility of the installer to
establish the maintenance procedures
using the manufacturer documentation.
Preventive Maintenance:Vacuum
cleaning of the Controller and the
external power amplifier(s) every +/- 2
years (depending on the ambient
dust).When used, vacuum clean the
rack mounting filters of the cooling
fans +/- 2 years (depending on the
ambient dust).Prevent or remove
animal nests (mice and rats can eat the
cabling).
Compliant. For this purpose retain the
original data sheets and the Installation
and Operation manuals.
Responsibility of the installer.
N/a
Responsibility of the installer.
Responsibility of the installer.
9922 141 1037x (V2.16) | V0.6 | 2011.09