Clause / Requirement
5.3 Indication on alphanumeric
displays
Where an alphanumeric display is used to
display indications relating to different
functional conditions these may be displayed
at the same time. However, for each functional
condition there shall be only one window, in
which all of the information relating to that
functional condition is grouped.
5.4 Indication of the supply of power
5.4.1 A visible indication shall be given by
means of a separate discrete light-emitting
indicator while the VACIE is supplied with
power.
5.4.2 Where the VACIE is distributed in more
than one cabinet, an indication of supply of
power to each distributed cabinet shall be
given at that point.
5.5 Additional indications
Where additional indications are provided, they
shall be clearly identifiable and shall not
override the primary indication of the VACIE.
Bosch Security Systems B.V.
Compliance
Not applicable.
The front panel of the controller and
remote control panels have a field with
LEDs that have specific fault assigned to
them. Each zone has a separate LED to
signal a fault in that zone.
If a zone on a router is in fault condition.
The main controller will signal a router fault
and the router will indicate which zone.
The logging application delivered with the
Plena Voice Alarm System offers a
graphical user interface for viewing events
(Logging Viewer).
Plena Voice Alarm System is compliant.
Each Plena Voice Alarm System component
has a dedicated power LED.
The Plena Voice Alarm System can be
distributed in more than one cabinet,
depending on the installation of the
system. Many system components can be
mounted in a 19'' rack. Each cabinet will
indicate supply of power independently if
the system is distributed in more than one
cabinet.
Plena Voice Alarm System is compliant.
For LEDs with multiple indication
functions, all of the additional indications
are clearly identified (in the Installation
and User Instructions of the Plena Voice
Alarm System); since the fault warning
indication and the voice alarm indication
always have precedence over the
additional indications, the primary
indications are not overridden.
Almost all LEDs indicate a single function.