Setting Auxiliary Switches

ATTENTION
Referring to Figure 31. The first two cams (starting from the front) are for the 0% and
100% end of travel limit switches (Switches #1 and #2) and should not need any
adjustments as they are factory set to stop the actuator precisely at 0% and 100%. See
Setting End-of-Travel Limit Switches (page 78).
Additional switch settings should be set so that switch #3 operates in synchronism with switch
#1 (i.e., both activating when the actuator is going in the same direction) and switch #4 to
operates in synchronism with switch #2, etc. See Figure 32 for auxiliary switch settings.
LEFT HAND
POINTER SCALE
SW #3
SW #4
SW #5
SW #6
If it becomes necessary to do adjust the auxillary switch cams in the field, use the procedure given in Table
33.
Revision 6
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/07
0%
17 (SW3 COM)
18
NO
19
24
NO
25

Figure 32 Auxiliary Switch Settings

While the unit is powered, a potentially lethal shock hazard exists inside the case.
(SW 6 COM) 26
23 (SW5 COM)
NC
NC
NC
NC
Set Up and Calibration Procedures
Setting Auxiliary Switches
100%
20 (SW4 COM)
16
21
NO
22
27
NO