Honeywell 2000 Series Installation, Operation And Maintenance Manual page 16

Herculine 2000 series
Hide thumbs Also See for 2000 Series:
Table of Contents

Advertisement

Specifications
Technical and Operating Specifications
Mains Supply
Motor
Motor Current
Loss of Power
Local Auto/Manual Switch
End of travel Limit
Switches
Auxiliary Switches/Relays
Approvals
Enclosure Rating
Clamp Bolt
Electrical and Performance Specifications
Input Signals
Isolation
Load Requirement (4-20)
Input Impedance
Feedback
6
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
100-130 Vac single phase, 50 Hz or 60 Hz
200-240 Vac single phase, 50 Hz or 60 Hz
Instant start/stop, non-coasting, non-burnout, continuous duty, permanent
magnet, synchronous induction motor. Can be stalled up to 100 hours without
damage.
= No load = full load = locked rotor = 0.4 amp for 120Vac, 0.2 amp for 240 Vac
Stays in place on loss of power
Optional – Allows local and automatic operation of the actuator.
Standard – adjustable to limit actuator travel to less than 90 or 150 degrees
respectively
Optional – Up to 4 additional SPDT switches rated at (10 A at 125 Vac, 5 A at 250
Vac).
Certifications
CSA/UL (Standard)
CE Compliant (optional)
Type 4 (NEMA 4), IP66 (standard)
Torque Settings of Crank Arm Bolts
88 lb-in (10 N-m)
®
HercuLine
2002
Analog:
0/4 to 20 mA (With CPU
PWA jumper in current
position)
0/1 to 5 Vdc
0 to 10 Vdc
Digital:
Modbus RTU (RS485)
Input signal, output signal and power are isolated from each other.
Current Out — 0 to 1000 ohms
0/4 to 20 mA
0/1 to 5 Vdc
0-10 vdc
0 to 20 mA, 4 to 20 mA
0 to 5 Vdc & 1 to 5 Vdc with 250 ohm resistor, (0 to 16 Vdc with 800
ohm resistor)
Electrical
®
HercuLine
Analog:
0/4 to 20 mA (With CPU
PWA jumper in current
position)
0/1 to 5 Vdc
0 to 10 Vdc
Series 90 control
Digital:
Modbus RTU (RS485)
250 ohms
10 K ohms
2001
HercuLine
120 vac drive open/120 vac
drive close
240 vac drive open/240 vac
drive close
NA
NA
NA
Dual output 1000 ohms
over 90 degrees (135 ohms
with 158 resistor)
Dual output 1000 ohms
over 150 degrees (135
ohms with with 158 resistor)
®
2000/2003
Revision 6
7/07