Table 30 Potentiometer Position Sensor Calibration Procedure - Honeywell 2000 Series Installation, Operation And Maintenance Manual

Herculine 2000 series
Hide thumbs Also See for 2000 Series:
Table of Contents

Advertisement

Set Up and Calibration Procedures
Calibration
Step
Remove AC power to the actuator.
1
Remove the six screws and the top cover from the actuator case. See Figure 2.
2
Lay extended cover assembly on a flat surface. Remove relay cards if present.
Reapply AC power to the actuator.
3
Press SET UP key to access the INPUT set up group.
4
Press FUNCTION key until the lower display reads Direct.
Press the
NOTE: Actuator direction must be set to CCW for this procedure. Direction can be changed
after calibration is complete.
Drive the actuator to the 50% position (this refers to the position on the actuator scale for CCW
5
rotation). This should be done manually with the handwheel or with the AUTO - MANUAL
switch.
Press SET UP key until the display reads CAL POSOUT.
6
Press the FUNCTION key until the dispaly reads DIS CALPOS.
Press the
Press FUNCTION key.
The upper display now shows the output of the position sensor in Volts.
Loosen the set screw at the end of the switch camshaft where the potentiometer connects to
7
the shaft.
Using pliers, adjust the white plastic knob on the back side of the potentiometer so the voltage
8
in the local display is 2.500 ± 0.010 volts dc.
Tighten set screw with an allen wrench.
9
Press DISPLAY key to exit calibration mode.
10
Remove AC power to the actuator. Reinstall relay cards If present.
11
Install a new gasket and replace extended cover. Secure to actuator with screws.
12
Continue with calibration procedure in Table 31.
13
76
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Table 30 Potentiometer Position Sensor Calibration Procedure

or
keys to set Actuator Rotation direction to CCW.
or
keys until the lower display reads BEGN CALPOS.
Action
Revision 6
7/07