Digital Input Set Up Group

Table 17 lists the parameters and selections availible for the SET DIGINP group.
Actuator Lower
Display
Prompt
DIGINP
EndPos
Revision 6
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/07

Table 17 Digital Input Set Up Group Parameters

Selections or
Range of Setting
Digital Input State — Selects the position of the actuator in
response to a digital input signal (contact closure).
None — No action by the actuator.
NONE
Up — Actuator motor moves to full scale value.
UP
Down — Actuator motor moves to zero value.
DOWN
User selected value — Actuator motor moves to a
USER
customer-selected value.
default = UP
* Allows setting of End Position Value.
END POSITION VALUE — (DIGINP USER only) Selects the
0 – 100
(in percent)
motor position you want the actuator to go to when digital
input signal present (contact closure).
Set Up and Calibration Procedures
Parameter Definition/PDA HercuLink
Digital Input Set Up Group
®
Prompt
51