6.5

Remote Contact

A remote contact interface is a standard feature on the Premium and Seismic units, and is available as
dry switch contacts through a DB9 male connector located on the front of the UPS.
Figure 6-9 shows the contact state and pin assignment for each signal and the associated DB9 connector
pin out.
WARNING
Notes:
1) Pin "switches" are shown in their inactive states. Example: (if battery voltage is low, pin 7 will
be connected to System Common).
2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps.
3) Pin number "3" is not used.
4200FA Installation and Operation Manual
5 System Common
6 Bypass Active
7 Battery Voltage Low
8 UPS On-line
9
Battery Discharge
4
1
Fault Signal Detect
2
50kVA LT units: Only Authorized Personnel may access the remote
contact DB-9.

Figure 6-9 DB-9 Pin Assignments

DB9 Male Connector Outline
(Facing connector)
1
2
3
4
5
6
7
8
9
35