Toshiba 4200FA Installation And Operation Manual page 97

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Display
EE1ST
EEPROM is loaded with default values.
EPO
EPO circuit is active.
EQCHRG
Equalized Charging
FLT
A fault has occurred.
FRCDBYP
UPS forced into bypass mode.
FWUPD
Firmware updated.
INVSTUP
UPS starts up in inverter mode (skips
bypass)
INV
Inverter mode.
LANSD
UPS goes to Shutdown triggered from LAN
SD (shutdown) circuit.
LB
Low Battery – The battery voltage has
dropped low (about 90% or less) during
operation. Continued operation in this mode
will deplete battery and cause output shut
down. (This can be adjusted by the operator
LCRUN
Local run command issued.
MANUAL
UPS is in Manual mode
OUT50HZ
UPS set for 50 Hz Output.
PFAIL
Input power failure.
PRCHRG
Protective charging
RMRUN
Remote Run command issued.
RMTSD
Remote shutdown occurred.
RMTSWEN
Remote switch control enable.
SYN
Synchronous mode.
TIMEDSD
UPS is counting down prior to shutdown.
WRN
A warning has occurred.
4200FA Installation and Operation Manual
Meaning
Action
No action needed.
Reset EPO switch to start.
No action needed.
See Fault records.
Secure the load and contact the
nearest Toshiba authorized
representative for service.
No action needed.
No action needed.
Inverter is running (it can be On-Line,
Battery Test, or Backup)
Deactivate LAN shutdown signal to
reset.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
No action needed.
No action needed.
No action needed.
No action needed.
No action needed.
No action needed.
One or more warnings occurred.
Check the Warnings field for details.
Disconnect LAN signal to reset.
No action needed.
Input and output are synchronized.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
See Warning record.
85