Communication Interface; Remote Contact - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 15/ 25/ 30/ 33/ 50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

4.5

Communication Interface

4.5.1 Remote Contact

This interface is a standard feature and is available as dry switch contacts through a DB9 male
connector located on the front of the UPS. The following schematic shows the contact state
and pin assignment for each signal and the associated DB9 connector pin-out.
Notes:
1) Pin "switches" are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be
connected to System Common).
2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps.
3) Pin number "3" is not used.
TOSHIBA
5 System Common
6 Bypass Active
7 Battery Voltage Low
8 UPS On-line
9
Battery Discharge
4
1
Fault Signal Detect
2
28
DB9 Male Connector Outline
(Facing Connector)
1
2
3
4
5
6
7
8
9

Advertisement