Bypass Mode; Figure 8-2 Power Flow In Bypass Mode - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

8.2

Bypass Mode

If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched from the
main circuit to the Bypass circuit. Power flow through the bypass is shown in the following illustration.
This changeover occurs automatically in less than 4 milliseconds in phase (Make-Before-Break).
If the power flow is transferred to the Bypass circuit because of an overload, and that overload condition ends within a
specified period of time, then the power flow will "re-transfer" to the AC Input Mode (Normal Operation) automatically.
If the power flow is transferred to the Bypass circuit due to a fault condition, then the power flow must be
transferred manually from the UPS's Bypass circuit back to the Inverter circuit after repairing the fault (see
"Start-up Procedure").
If the power flow is transferred to the Bypass circuit due to an overload condition, then the power flow will
automatically transfer from the UPS's Bypass circuit back to the Inverter circuit after removing the overload
(see "Overload Operation").
Power Flow
Input
Isolating
Power
XFMR
58
(Not available for LT units)
MCCB
Converter

Figure 8-2 Power Flow in Bypass Mode

MBS
Bypass
Inverter
Charger/
Chopper
External
Batteries
4200FA Installation and Operation Manual
Output
Power