Table 6.4 Bypass Wire Size - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Minimum / Maximum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input TB4 15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
208 V
220 V
240 V
380 V
400 V
415 V
480 V
600 V
*Maximum Wire Size is 1 AWG.
4200FA Installation and Operation Manual

Table 6.4 Bypass Wire Size

15 kVA
AWG*
Torque
AWG*
8 – 1
51 in-lbs.
4 – 1
8 – 1
51 in-lbs.
4 – 1
8 – 1
51 in-lbs.
4 – 1
10 – 1
35 in-lbs.
8 – 1
10 – 1
35 in-lbs.
8 – 1
10 – 1
35 in-lbs.
8 – 1
10 – 1
35 in-lbs.
8 – 1
10 – 1
35 in-lbs.
10 – 1
25 kVA
30 kVA
Torque
AWG*
51 in-lbs.
2 – 1
51 in-lbs.
2 – 1
51 in-lbs.
2 – 1
51 in-lbs.
6 – 1
51 in-lbs.
6 – 1
51 in-lbs.
6 – 1
51 in-lbs.
6 – 1
35 in-lbs.
10 – 1
Torque
87 in-lbs.
87 in-lbs.
87 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
35 in-lbs.