Toshiba 4200FA Installation And Operation Manual page 129

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Blk
Item
Long Description
2
9
Output Phase Current (C)
2
10
Output Frequency (A)
2
11
Output Frequency (B)
2
12
Output Frequency (C)
2
13
Output Power W (Total)
2
21
Output Voltage % (A)
2
22
Output Voltage % (B)
2
23
Output Voltage % (C)
2
24
Output Current % (Total)
2
25
Output Current % (A)
2
26
Output Current % (B)
2
27
Output Current % (C)
2
28
Output Power W % (Total)
2
36
Output Power Factor
2
40
No of Output Line
2
41
Rated Line to Line Output Voltage
2
42
Rated Line to Neutral Output Voltage
4200FA Installation and Operation Manual
Short Description
Units
(Inside UPS)
Current (C)
A
Freq (A)
dHz
Freq (B)
dHz
Freq (C)
dHz
Power W (Total)
kW
Voltage % (A)
%
Voltage % (B)
%
Voltage % (C)
%
Current % (Total)
%
Current % (A)
%
Current % (B)
%
Current % (C)
%
Power W % (Total)
%
Power Factor
No of Output Line
Rated Voltage L-L
V
Rated Voltage L-N
V
Permissions
Remark
User
Admin
R
R
R
R
600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
R
R
600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
R
R
600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
R
R
R
R
Percentage of Line to Line and Line
to Neutral Voltage are the same
R
R
Percentage of Line to Line and Line
to Neutral Voltage are the same
R
R
Percentage of Line to Line and Line
to Neutral Voltage are the same
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
RE
III
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
117

Advertisement

Table of Contents
loading

Table of Contents