Toshiba 4200FA Installation And Operation Manual page 53

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Environment
Efficiency (Typical)
Heat Loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
3
Altitude
1 – Specified at rated conditions under balanced linear loads.
2 – Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. An initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
3 – At 6600 ft. (2000 m) above sea level, output capacity should be derated by 3% (Consult factory for higher elevations).
4 – Prolonged operation at this level requires derating of the maximum Operating Temperature to 90 °F ( 32 °C).
5 – SHORT TERM operation only (e.g. Brownouts). Operation at this level requires derating the maximum Operating Temperature to 95 °F ( 35
°C).
4200FA Installation and Operation Manual
AC/DC/AC – See Table 5.10,
DC/AC: 86%
See Table 5.10
60dB (A) at 1 meter from the front of the unit
32 –104 °F (0 – 40 °C); optimal temperature is 77 °F (25 °C)
30 – 90% RH (non condensing)
Less than 2000 meters
AC/DC/AC – See Table 5.10,
DC/AC: 87%
See Table 5.10
3
41