System Warning Messages; Table 9.14 System Warning Messages - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

9.23

System Warning Messages

Warning messages are generated when a noncritical abnormal operating condition occurs. The following
tables shows possible messages and their meaning.
When a Warning condition exists, the amber LED on the UPS display panel will flash for the duration of
the Warning condition
Display
ASYN
Asynchronous mode – Input and output
frequency are different. Bypass is disabled.
BLFEND
Battery Lifetime End – Batteries at end of life.
BLFNE
Battery Lifetime Near End – Batteries are
nearing the end of their expected lifetime.
BMCCBO
Battery MCCB is OFF - Backup power is not
available.
BOH
Battery Overheat – Battery not within
specifications.
BTFAIL
Battery Test Failed – Battery not within
specifications.
BYP
UPS is in bypass mode.
CALL
Service Call Required – Inspection of the unit
is advised.
COV
Charger Overvoltage – Battery Charger not
within specifications.
CL
Current Limit – UPS not within specifications.
EEUPDER
EEPROM Update error.
EE2RAER
EEPROM to ROM loading error.
FIBYER
Input/Bypass Frequency Error – Input
frequency outside of UPS specifications.
INVOL
Inverter overload.
MCCBTRP
UPS input MCCB tripped open.
NOCOM
No communication between main controller
and display.
OL110
Overload – UPS is overloaded (110% and
above) Unit will switch to bypass operation or
shut down if no action is taken.
REYDNER
RemotEye III Downlink error (main and
communication error).
REYEUPER
RemotEye III Uplink error.
RO2EEER
ROM to EE error.
SOH
System overheat.
4200FA Installation and Operation Manual

Table 9.14 System Warning Messages

Meaning
Action
No Action Needed.
Have batteries replaced immediately.
Contact the nearest Toshiba
authorized representative to arrange
for battery replacement.
Switch Battery Breaker ON.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Switch UPS On-Line.
Have inspection/service performed.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Depends on UPS mode.
Shutdown excess load equipment to
reduce load.
Contact the nearest Toshiba
authorized representative for service.
Shut down excess equipment to
reduce load.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
Contact the nearest Toshiba
authorized representative for service.
83

Advertisement