Figure 4-19 Remote "Start" Contact Connections - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Activated when the inverter output contactor 52C has closed.
NOTE: The UPS is equipped with a selectable output contact feature.
The above alarms are the default settings.
Contact TOSHIBA International Corporation for setup information.
B) Input Contacts (for remote access to UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 12Vdc.
Provide external dry contact accordingly.
CAUTION:
Damage to UPS may result.
Refer to Figure 4-19 for a typical wiring configuration. Although this figure applies to the remote
start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and
battery temperature high.
UPS Cabinet
Relay Coil current : 16.7 mA
28
Do not apply voltages to remote access input terminals.
Relay
Coil
12 VDC

Figure 4-19 Remote "Start" Contact Connections

G9000 Installation and Operation Manual – 61480-012
External to
UPS Cabinet
Start
Start
Switch
Common
ON
OFF
Use Momentary
Switches Only
User supplied
0.5s – 4s