4.2

Communication Interface

4.2.1

Remote Contact

The remote contact interface is a standard feature and is available as dry switch contacts
through a DB9 male connector located under the Remote Eye Cover on the front of the UPS
(see Section 4 for location). The following schematic shows the contact state and pin
assignment for each signal and the associated DB9 connector pin-out.
Notes:
1) Switches are shown in their inactive states (if battery voltage is low pin 7 will be connected to System
Common).
2) Contacts are resistive loads rated at 30 VDC, 0.1 A (125 VAC, 3 A).
3) Pin 3 is not used.
4200 FA User's Manual
TOSHIBA
5 System Common
6 Bypass Active
7 Battery Voltage Low
8 UPS On-line
9
Battery Discharge
4
1
Fault Signal Detect
2
DB9 Male Connector Outline
(facing connector)
1
2
3
4
5
6
7
8
9