4.3

Communication Interface

4.3.1

Remote Contact

The remote contact interface is a standard feature and is available as dry switch
contacts through a DB9 male connector located on the back side of the UPS (see
Section 9 for DB9 connector location). The following schematic shows the contact
state and pin assignment for each signal and the associated DB9 connector pin-
out.
Notes:
1) Switches are shown in their inactive states (if battery voltage is low pin 7 will be connected to System
Common).
2) Contacts are resistive loads rated at 30 VDC, 0.1A (125VAC 3A).
3) Pin 3 is not used.
T O S H I B A
5 System Common
6 Bypass Active
7 Battery Voltage Low
8 UPS On-line
9
Battery Discharge
4
1
Fault Signal Detect
2
30
DB9 Male Connector Outline
(facing connector)
1
2
3
4
5
6
7
8
9