Toshiba 4200FA Installation And Operation Manual page 18

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Rated Output
240 VAC
240 V, 45 A
380/220 VAC
480 V, 30 A
480/277 VAC
480 V, 25 A
600 VAC
600 V, 20 A
The maximum ambient temperature in which the Uninterruptible Power System (UPS) should be operated
is 104 °F (40 °C) without batteries and 89 °F (32 °C) if the battery cabinet is subject to the same ambient
temperature as the UPS. The nominal battery voltage for all internal battery models is 288 VDC. The
nominal battery voltage for all external battery models is 288 VDC.
An Authorized TOSHIBA Representative who is knowledgeable of batteries and the required precautions
should perform service on the batteries. Keep unauthorized personnel away from batteries.
Refer to the Battery System Manual when scheduling battery maintenance or battery replacement.
DANGER
indirect, or consequential damage or injury that may result from the misuse of this equipment.
CAUTION
CAUTION
CAUTION
CAUTION
WARNING
WARNING
6
15 kVA
25 kVA
Rating
Rating
240 V, 80 A
480 V, 50 A
480 V, 40 A
600 V, 30 A
Misuse of this equipment could result in injury and equipment damage.
In no event will TOSHIBA be responsible or liable for direct,
Do not dispose of the batteries in a fire. The batteries may
explode.
Do not open or mutilate the batteries. Released electrolyte is toxic and
harmful to the eyes and skin.
This unit contains sealed lead acid batteries. An annual preventative
maintenance should be performed by an authorized technician.
Failure to do so could result in batteries exploding and emitting gasses.
Do not open or mutilate the batteries. Released electrolyte is toxic and
harmful to the eyes and skin.
Failure to replace a battery before it becomes exhausted may cause
the case to crack, possibly releasing electrolytes from inside the
battery, and resulting in secondary faults such as odor, smoke, and
fire.
Only personnel knowledgeable of batteries and the required
precautions should perform installation and servicing of batteries.
Keep
Unauthorized personnel away from the batteries.
30 kVA
Rating
240 V, 90 A
240 V, 150 A
480 V, 60 A
480 V, 100 A
480 V, 45 A
480 V, 80 A
600 V, 40 A
600 V, 60 A
4200FA Installation and Operation Manual
50 kVA
Rating