4200Fa 15/25 Kva W/Internal Transformer - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

7.3

4200FA 15/25 kVA w/Internal Transformer

Model Number
Rated Output Capacity
External Dimensions
W x D x H (cm)
Input
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
Harmonic Currents
Battery
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
Rated Back-up Time
Rated Charge Current
Output
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 ms)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
42
# =(B: 208; H: 220; C: 240; N: 380–415 ∆-wye; P: 380–415 wye;
Input
Outpu
*=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye:
t
w/ casters: 20.0" x 36.3" x 59.7"(50.8 cm x 92.2 cm x 151.6 cm)
w/o casters: 20.0" x 36.3" x 60.0"(50.8 cm x 92.2 cm x 152.4 cm)
4,5
1
Less than 8 times the rated current under synchronous operation
1
2
± 5% (0 – 100% balanced load); ± 6% (0 – 100% unbalanced load)
C42#3*150#AMXN, -S
D: 480; M: 600) VAC
M:600) VAC
15 kVA
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
+10% to -15%; (-10% to -15%)
50/60 Hz
3 phase ; 3 Wire + GND
3 phase ; 4 Wire + GND
Greater than 0.98 when in inverter mode
16 kVA
From 20% to 100% over 5 seconds
115% maximum
1
Less than 8.5%
288 VDC (216 – 332 VDC)
324.0 VDC (± 2%)
0.5 V R.M.S.
Refer to Battery System Manual
10.0 Amps
(Determined by Output Transformer internal to the unit)
VA / Nominal Output Voltage / 1.73
0.8 lagging
3 phase ; 4 Wire + GND
± 5V Manually from key pad
± 2° (0 –100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)
switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change);
± 3% (loss or return of input voltage);
± 8% (transfer from bypass to inverter)
125% for 90 sec; 150% for 30 sec
1000% for 10ms; 125% for 10 min.
2.5 – 3.0 within the kW range
1.73 times line rating
4200FA Installation and Operation Manual
C42#3*250#AMXN, -S
25 kVA
4
5
, (-15 to -30%)
1
26 kVA
1
Less than 5.5%
2

Advertisement

Table of Contents
loading

Table of Contents