Toshiba 4200FA Installation And Operation Manual page 125

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Installation Planning Guide for 15-50kVA UPS
Standard System: 480V Input, 480/277V Output
For Maximum cable sizes, see Note 7.
UPS kVA/ kW Rating
15 kVA/12 kW
25 kVA/ 20 kW
30 kVA/ 24 kW
50 kVA/ 40 kW
Maximum Input Power
Demand
kVA
PF
Amps
15
>0.97
21
25
>0.97
32
30
>0.97
38
50
>0.97
61
Battery Capacity Required
Maximum Discharge
for Full Load Output
kWB
15
15
25
24
30
29
50
47
Rated Output Power
kVA
PF
Amps
15
0.8
18
25
0.8
30
30
0.8
36
50
0.8
60
4200FA Installation and Operation Manual
General Mechanical Information
Dimensions
(W x D x H)
Inches
20 x 36.3 x 59.7
20 x 36.3 x 59.7
20 x 36.3 x 59.7
35.5 x 38.3 x 59.3
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External Feeder
Breaker
Amps
30A
45 A
60 A
80 A
Battery Input (288VDC Nominal)
Suggested External
at Full Load Output
Feeder Breaker
Amps DC
Amps
64
70 A
105
110 A
126
150 A
204
225 A
AC Output (480/277V 3-Phase / 4-Wire)
Suggested External Feeder
Breaker
Amps
25 A
40 A
45 A
75 A
Weight
Lbs.
988
998
1003
1941
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 10
(1) x 8
(1) x 8
(1) x 4
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 4
(1) x 1
(1) x 1
(1) x 250
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 10 / (1) x 8
(1) x 8 / (1) x 6
(1) x 8 / (1) x 4
(1) x 4 / (1) x 2
Approximate Full-Load
Heat Loss
kBTU's / Hr
7.2
10.5
14.3
22.6
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
480
480
480
480
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
70
70
70
70
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
113

Advertisement

Table of Contents
loading

Table of Contents