NOTE
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is
24VDC. Provide external dry contact accordingly.
PROHIBIT
Refer to Figure 2.12 for a typical wiring configuration. Although this figure applies to the remote
start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and
battery temperature high.
FIGURE 2.12
UPS Cabinet
Relay Coil current : 8.3mA
G9000 Installation and Operation Manual
The UPS is equipped with a selectable output contact feature.
The above alarms are the default settings.
Contact Toshiba International Corporation for setup information.
Do not apply voltages to remote access input terminals.
Damage to UPS may result.
Remote "Start" Contact Connections
Relay
Coil
24 VDC
External to UPS
Cabinet
Start
Common
Use Momentary Switches Only
User supplied
Start
Switch
0.5S- 4S
ON
OFF