PREMIER SX INSTALLATION MANUAL.

1.INTRODUCTION

THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND
BE EARTHED
This equipment must be installed and maintained by a qualified and technically experienced person.

1.1 HANDLING THE PCBS

If the PCBs are to be removed to ease fitting the enclosure and cables, care must be taken to
avoid damage by static.
The best method is to wear an earth strap, but touching any earth point (eg building plumbing) will
help to discharge any static. Hold PCBs by their sides, avoiding contact with any components.
Always handle PCBs by their sides and avoid touching the legs of any components. Keep the PCBs
away from damp dirty areas, e.g. in a small cardboard box.

1.2 USING THIS MANUAL

This manual explains, in a step-by-step manner, the procedure for the installation of the Premier SX
Range of Fire Alarm Control Panels. For full operational and maintenance information, please refer
to document GLT.MAN-102 (USER MANUAL, MAINTENANCE GUIDE & LOG BOOK). It also
contains a System set-up table, and Installation Certificate, that must be completed by the
Commissioning Engineer prior to system handover.
Unlike the User Manual, this Installation Manual must not be left accessible to the User.
1.3 ABOUT THE PREMIER SX FIRE ALARM CONTROL PANEL & INTEGRAL PSE
• The PREMIER SX Fire alarm control panel is
available in 1,2,4,6 or 8 Zone sizes.
• It has 2 sounder output circuits each capable of
supplying 400mA.
• It has a set of fire relay contacts (voltage free) rated
at 1A SELV.
• It has a set of fault relay contacts (voltage free)
rated at 1A SELV. This relay is normally
powered to allow a fault output in the case of
total power failure.
• It has a class change connection to allow remote
activation of the sounders. (not required by
EN54-2)
• It has the ability to disable any zone or the sounder
circuits.
• It has a one man test mode, which resets the zone
in test after 7 seconds.(EN54 option with
requirements)
• It has a sounder delay facility (0-9 minutes in 1
minute steps). (EN54 option with requirements)
• It has a maximum battery capacity of 7 Ah.

1.4 DESIGNING THE SYSTEM

This manual is not designed to teach Fire Alarm System design. It is assumed that the installer has
an understanding of Fire Alarm System components and their use.
We strongly recommend consultation with a suitably qualified, competent person regarding the
design of the Fire Alarm System. The System must be commissioned and serviced in accordance
with our instructions and the relevant National Standards. Contact the Fire Officer concerned with
the property at an early stage in case he has any special requirements.
If in doubt, read BS 5839: Pt 1: 2002 "Fire Detection and Fire Alarm Systems for buildings (Code of
Practice for System Design, Installation, Commissioning and Maintenance)" available from the BSI,
or at your local reference library.

1.5 EQUIPMENT GUARANTEE

If this equipment is not fitted and commissioned according to our guidelines, and the relevant
National Standards, by an approved and competent person or organisation, the warrantee may
become void.
Approved Document No: GLT.MAN-101
Issue : 1.95
Authorised: GH
• It has an in built capability of operating with Diode
• It will operate in ambient temperatures of –5 to
• It will operate in a relative humidity of up to 93%
• It will withstand vibrations between 5 & 150 Hz
• It has a maximum capacity of 32 devices per zone
• The PSE is linear, with a 1.1A output at system
• The mains supply is filtered before entering the
• The charger & battery are both fused at 1.6A
• The PSE will draw a maximum of 25uA from the
• The FACP & PSE should be maintained as
Date: 09/06/2004
bases (for line continuity on head removal).
o
40
C
(non condensing)
voltage (18-32V)
transformer.
(Quickblow)
battery in the event of mains failure. (the FACP
will continue to take around 60mA)
described in section 3 of the User Manual,
Maintenance Guide & Log Book.
MUST
PAGE 3