Actual less than or
"Actual is less than or equal to setpoint configuration" means that the DP/
equal to setpoint
ASi link compares the actual configuration with the setpoint configuration. If
configuration
the DP/ASi link detects any differences, it reacts in two different ways:
If no difference is detected between actual and setpoint configurations, the
DP/ASi link starts up normally.
Parameterization
Bytes 16 to 139 contain the parameterization data for the ASi slaves. The
data for ASi slaves
method of determining the parameterization data is described in section C.2.
Precisely four bytes are assigned to every ASi slave.
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
If the DP/ASi link detects unconfigured ASi slaves, it behaves in the same
way as for "actual is equal to setpoint configuration".
If ASi slaves are missing from the actual configuration compared to the
setpoint configuration – without unconfigured ASi slaves being present –
the DP/ASi link reports a configuration error. Data exchange is initiated,
however.
Parameterization Message
C-5