Siemens SIMATIC HMI Mobile Panel 277 RO Operating Instructions Manual

Hmi device
Table of Contents

Advertisement

Mobile Panel 277 RO
SIMATIC HMI
HMI device
Mobile Panel 277 RO
Operating Instructions
10/2015
A5E36824256-AA
___________________
Preface
___________________
Overview
Safety instructions and
___________________
general notes
___________________
Planning application
___________________
Mounting and connecting
___________________
Operator controls and
displays
___________________
Configuring the operating
system
___________________
Using RemoteOperate Client
___________________
Backing up and restoring
data
___________________
Maintenance and care
___________________
Technical specifications
___________________
Appendix
___________________
Abbreviations
1
2
3
4
5
6
7
8
9
10
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC HMI Mobile Panel 277 RO

  • Page 1 ___________________ Mobile Panel 277 RO Preface ___________________ Overview Safety instructions and ___________________ SIMATIC HMI general notes ___________________ Planning application HMI device Mobile Panel 277 RO ___________________ Mounting and connecting ___________________ Operator controls and displays Operating Instructions ___________________ Configuring the operating system ___________________ Using RemoteOperate Client...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    Preface Purpose of the operating instructions These operating instructions provide information based on the requirements defined by DIN EN 62079 for mechanical engineering documentation. This information relates to the place of use, transport, storage, mounting, use and maintenance. These operating instructions are intended for the following user groups: ●...
  • Page 4 Preface Associated documents Additional information on the RemoteOperate V4 software is available in the RemoteOperate V4 programming manual. Pictures The HMI device is sometimes shown in the form of photographs in these operating instructions. The photographs of the HMI device may differ slightly from the factory state of the HMI device.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................3 Overview ..............................9 Product overview ........................9 Design of the HMI device ......................9 Accessories ..........................12 1.3.1 Connecting cable ........................12 1.3.2 Connection box ........................13 1.3.3 Rechargeable buffer battery ....................14 1.3.4 Wall-mounting bracket ......................
  • Page 6 Table of contents Mounting and connecting ......................... 39 Checking the package contents ..................... 39 Mounting the connection box and wall-mounting bracket ............39 Electrical installation ......................41 Connecting the connection box ....................41 4.4.1 Overview ..........................41 4.4.2 Opening and closing the connection box ................42 4.4.3 Stripping the insulation of cables ...................
  • Page 7 Table of contents Changing HMI device settings ....................85 6.5.1 Setting the date and time ......................85 6.5.2 Backup registry information ....................87 6.5.3 Changing monitor settings ...................... 88 6.5.4 Setting the screen saver ......................89 6.5.5 Restarting the HMI device ...................... 91 6.5.6 Displaying information about the HMI device .................
  • Page 8 Table of contents Technical specifications ......................... 127 10.1 Dimension drawings ......................127 10.1.1 Mobile Panel 277 RO ......................127 10.1.2 Wall-mounting bracket ......................129 10.1.3 Connection box PN Plus ...................... 130 10.2 Specifications ........................131 10.2.1 Mobile Panel 277 RO ......................131 10.2.2 Rechargeable buffer battery ....................
  • Page 9: Overview

    Overview Product overview Expanded application options – with Mobile Panel 277 RO SIMATIC Mobile Panels offer the option of making safety functions available on a mobile basis at any point of a machine or plant. The Mobile Panel 277 RO enables you to use text or graphically based projects even more efficiently for simple and medium-complexity control and monitoring tasks on machines and plants.
  • Page 10 Overview 1.2 Design of the HMI device Front view of the Mobile Panel 277 RO ① STOP button ② Display with touch screen Side view of the Mobile Panel 277 RO ① Impact guards ② Enabling buttons, positioned on both sides of the Mobile Panel 277 RO ③...
  • Page 11 Overview 1.2 Design of the HMI device Rear view of the Mobile Panel 277 RO ① Rating label ② Pen holder with touch pen ③ Handle ④ Connection compartment cover ⑤ USB port and plugs ⑥ Cable inlet A touch pen is attached to the back of the HMI device. Accessory kit The accessory kit of the device includes: ●...
  • Page 12: Accessories

    Overview 1.3 Accessories Accessories 1.3.1 Connecting cable The Mobile Panel 277 RO is compatible with the connecting cable PN: ① Metallic push-pull circular connector ② Strain relief and antikink device for the connecting cable ③ RJ45 connector ④ Plug connector, 12-pin Connect the connecting cable to the Mobile Panel 277 RO so that it is not detachable.
  • Page 13: Connection Box

    Overview 1.3 Accessories 1.3.2 Connection box The Mobile Panel 277 RO is compatible with the connection box PN Plus: ① Screwed joint for process data line ② LEDs ③ Threaded assembly for power supply cable ④ Threaded assembly for cable with supplementary Stop and enabling button signals and for PLC-accompanying signals ⑤...
  • Page 14: Rechargeable Buffer Battery

    Overview 1.3 Accessories Division of the system into zones You can divide a system into various zones or functional areas by using numerous connection boxes. You can also set up the safety functions zone-dependently. This means that both enabling buttons and STOP buttons can act in only one particular zone and not in others.
  • Page 15: Wall-Mounting Bracket

    Overview 1.3 Accessories 1.3.4 Wall-mounting bracket The wall-mounting bracket provides a safe hold for the Mobile Panel 277 when used in stationary mode. ① Hook for the grip on the HMI device ② Screw flange The wall-mounting bracket is not included with the HMI device. The wall-mounting bracket is available under the article number 6AV6574-1AF04-4AA0.
  • Page 16: Usb/Ppi Cable

    HMI device. Only use the SD memory cards or multimedia cards tested and released by Siemens. A memory card is not included with the HMI device. The memory card can be ordered using the Siemens online catalog. For additional information, refer to the Internet at Industry Mall (https://mall.industry.siemens.com). Mobile Panel 277 RO...
  • Page 17: The Hmi Device In The Operating Process

    Overview 1.4 The HMI device in the operating process The HMI device in the operating process The HMI device is part of the operating process. The operating process is marked by three- way communication between the HMI device, server and PLC. The following figure shows an exemplary system design.
  • Page 18 Overview 1.4 The HMI device in the operating process The RemoteOperate software package Communication between the HMI device and the server is handled using the RemoteOperate software package. Using RemoteOperate you can monitor or operate a server from a client. The range of operations covers all the functions of the server.
  • Page 19: Safety Instructions And General Notes

    Safety instructions and general notes General safety instructions Safety regulations WARNING Personal injury or material damage due to non-compliance with safety regulations Strictly observe all instructions in these operating instructions at all times. Otherwise, hazardous situations can arise or the safety mechanisms in the HMI device can be rendered ineffective.
  • Page 20 Safety instructions and general notes 2.1 General safety instructions WARNING Operational reliability of the HMI device After a hard impact to the HMI device, check the safety-relevant features for functional capability, for example in the event that the HMI device is dropped. Manual actions performed with the HMI device may only occur in conjunction with the enabling buttons and at reduced velocity.
  • Page 21 2.2 Standards, certificates and approvals Industrial Security Siemens offers products and solutions with Industrial Security functions that support the safe operation of equipment, solutions, machines, devices and/or networks. They are important components in a comprehensive Industrial Security concept. As a result the products and solutions from Siemens are constantly evolving.
  • Page 22: Standards, Certificates And Approvals

    ● Directive 2006/42/EC of the European Parliament and Council dated 17 May 2006, on machinery, and amending Directive 95/16/EC (revised version) EC Declaration of Conformity The EC Declarations of Conformity are available to the relevant authorities at the following address: Siemens AG Digital Factory Factory Automation DF FA AS DH AMB Postfach 1963...
  • Page 23: Operating Safety

    Safety instructions and general notes 2.3 Operating safety Operating safety Standards The HMI device complies with the following standards: ● EN 60204-1 Safety of Machinery – Electrical Equipment of Machines ● EN 61131-1 and EN 61131-2 Programmable Controllers ● The HMI device was tested for EMC in accordance with the following standards: –...
  • Page 24: Voltage Supply

    Safety instructions and general notes 2.4 Voltage supply Voltage supply Safety specifications WARNING The HMI device corresponds to protection class III according to EN 61131-2 or EN 50178. The 24 VDC supply must be isolated from touch-hazardous voltages, for example by means of a safety isolation transformer or similar equipment.
  • Page 25: Risk Assessment

    Safety instructions and general notes 2.6 Risk assessment Risk assessment Performing risk assessment The following standards must be used to perform the risk assessment: ● EN ISO 12100:2010, General principles for design of machinery ● ISO 14121-1:2007, Risk Assessment for Machinery ●...
  • Page 26: Enabling Button

    Safety instructions and general notes 2.7 Enabling button Enabling button Introduction The enabling control device comprises the two enabling buttons mounted on both sides of the Mobile Panel 277 RO. Numerically controlled machines and systems are equipped with the operating modes "Automatic mode"...
  • Page 27 Safety instructions and general notes 2.7 Enabling button The Stop category of the enabling control device must be selected on the basis of a risk assessment and correspond to a Category 0 or 1 Stop. WARNING Conditions for the use of enabling buttons Enabling buttons may only be used if the person activating them promptly recognizes a danger to personnel and can immediately take steps to avoid the danger! Commands for unsafe conditions are not permitted to be issued with one enabling button...
  • Page 28: Stop Button

    Safety instructions and general notes 2.8 STOP button STOP button Safety instructions The STOP button on the HMI device brings about a safety-related stop of the system or machine in accordance with EN 60204-1:2006, Section 9.2.5.3. You have the option of implementing a Category 0, 1, or 2 Stop function in accordance with EN 60204-1:2006, Section 9.2.2.
  • Page 29: Electromagnetic Compatibility

    Safety instructions and general notes 2.9 Electromagnetic compatibility Electromagnetic compatibility Introduction The HMI device satisfies, among other things, the requirements of the EMC laws pertaining to the European domestic market. EMC-compliant installation The EMC-compliant installation of the connection box and the application of interference- proof cable is the basis for interference-free operation.
  • Page 30 Safety instructions and general notes 2.9 Electromagnetic compatibility Sinusoidal interference The following table shows the EMC behavior of the modules with respect to sinusoidal interference. This requires the HMI device to meet the specifications and directives for electrical installation. Sinusoidal interference Test values Degree of severity...
  • Page 31: Transport And Storage Conditions

    Safety instructions and general notes 2.10 Transport and storage conditions 2.10 Transport and storage conditions Mechanical and climatic transport and storage conditions The transport and storage conditions of this HMI device exceed requirements in accordance with IEC 61131-2. The following specifications apply to the transport and storage of an HMI device in its original packaging.
  • Page 32 Safety instructions and general notes 2.10 Transport and storage conditions Note In the following cases, ensure that no moisture can settle on or in the HMI device (dew): • Transportation of the HMI device in low temperatures • Under extreme temperature variations The HMI device must have acquired room temperature before it is put into operation.
  • Page 33: Planning Application

    Planning application Notes about usage Mechanical and climatic conditions of use The HMI device is designed for use in a location protected from the effects of the weather. The conditions of use are compliant with requirements to DIN IEC 60721-3-3: ●...
  • Page 34 Planning application 3.1 Notes about usage Testing mechanical ambient conditions The following table provides information on the type and scope of tests for mechanical ambient conditions. Tested for Test standard Comments Vibrations Vibration test in accordance Type of vibration: Frequency cycles at a rate of with IEC 60068, part 2–6 change of 1 octave/minute.
  • Page 35: Mounting Positions And Type Of Fixation

    Planning application 3.2 Mounting positions and type of fixation Climatic ambient conditions for the connection box The following table shows the permitted climatic ambient conditions for use of the connection box. Ambient conditions Permitted range Comments Temperature, operation From 0 to 50 °C Temperature, storage/transport From –20 to 70 °C Relative humidity, operation...
  • Page 36: Preparing For Mounting

    Planning application 3.3 Preparing for mounting Preparing for mounting Choose the mounting location for the wall-mounting bracket Observe the following points when selecting the mounting location: ● Position the wall-mounting bracket so that the display of the hooked-in HMI device is not exposed to direct sunlight.
  • Page 37: 3.4 Information On Insulation Tests, Protection Class And Degree Of Protection

    Planning application 3.4 Information on insulation tests, protection class and degree of protection The following clearances are required around the connection box PN Plus: Information on insulation tests, protection class and degree of protection Test voltages Insulation strength is demonstrated in the type test with the following test voltages in accordance with IEC 61131-2: Circuits with a nominal voltage of U to other circuits or ground...
  • Page 38: Rated Voltages

    Planning application 3.5 Rated voltages Rated voltages The following table shows the rated voltage and the corresponding tolerance range. Rated voltage Tolerance range +24 VDC 20.4 V to 28.8 V (–15 %, +20 %) Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 39: Mounting And Connecting

    Note Do not install parts damaged during shipment. In the case of damaged parts, contact your Siemens representative. The documentation belongs to the HMI device and is required for subsequent commissioning. Retain all enclosed documentation for the entire service life of the HMI device.
  • Page 40 Mounting and connecting 4.2 Mounting the connection box and wall-mounting bracket Note Positioning A position at eye level is recommended. This enables the Mobile Panel 277 RO to be operated when it is hooked into the wall-mounting bracket. Proceed as follows: 1.
  • Page 41: Electrical Installation

    Mounting and connecting 4.3 Electrical installation Electrical installation Electrical connections The electrical installation comprises the components: ● Connection box PN Plus ● Mobile Panel 277 RO You can connect the following devices or operator controls to these components: Device/Operator control Mobile Panel 277 RO Connection box Panel PC...
  • Page 42: Opening And Closing The Connection Box

    Mounting and connecting 4.4 Connecting the connection box Connection sequence Connect the connection box in the following sequence: 1. Equipotential bonding 2. Supply voltage NOTICE Connection sequence Always follow the correct sequence for connecting the connection box PN Plus. Non- observance can cause damage to the connection box PN Plus.
  • Page 43 Mounting and connecting 4.4 Connecting the connection box Procedure ① Screws ② Cover Proceed as follows: 1. Loosen the four marked screws. 2. Remove the screws and the cover. Protective cover ① Protective cover Note Protective cover Do not remove the protective cover. Otherwise there is a risk that the electronics of the connection box will be damaged or destroyed.
  • Page 44: Stripping The Insulation Of Cables

    The following figure shows you how to strip an Ethernet cable. Note Use a wire stripper as specified in the online catalog under Industry Mall (https://mall.industry.siemens.com) for fast and accurate stripping of the insulation. Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 45: Connecting The Equipotential Bonding Circuit

    Mounting and connecting 4.4 Connecting the connection box 4.4.4 Connecting the equipotential bonding circuit Potential differences Differences in potential between spatially separated system parts can lead to high equalizing currents via the data cables and therefore to the destruction of their ports. This situation may arise if the cable shielding is terminated at both ends and grounded at different system parts.
  • Page 46 Mounting and connecting 4.4 Connecting the connection box Connection graphic The following figure shows how to connect the equipotential bonding conductor to the connection box PN Plus. ① PE connection on the connection box (terminal strip 1, pin 1) ② Equipotential bonding conductor cross-section: 2.5 mm ③...
  • Page 47: Connecting The Server

    Mounting and connecting 4.4 Connecting the connection box 4.4.5 Connecting the server Connection graphic The following figure shows how to connect a panel PC to the HMI device as a server via the connection box. 4.4.6 Connecting the power supply The supply voltage for the HMI device is connected to a terminal strip in the connection box.
  • Page 48 Mounting and connecting 4.4 Connecting the connection box Connection graphic The following figure shows how to connect the power supply to the connection box PN Plus. The abbreviations in the figure are defined as follows: ● PE stands for protective conductor. ●...
  • Page 49: Connecting The Connecting Cable

    Mounting and connecting 4.4 Connecting the connection box 4.4.7 Connecting the connecting cable Introduction The connecting cable can be connected to the connection box with the help of a connector (metallic push-pull circular connector). The plug connector is coded anti-rotationally using a slot and key system.
  • Page 50 Mounting and connecting 4.4 Connecting the connection box Procedure for plugging in the connector Proceed as follows: 1. Retract the outer sleeve on the plug connector. 2. Plug the connector with retracted outer sleeve into the socket of the connection box. 3.
  • Page 51: Connecting The Mobile Panel 277 Ro

    Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO Connecting the Mobile Panel 277 RO 4.5.1 Connecting the HMI device Connecting the cables When connecting the cables, ensure that the contact pins are not bent. Secure the connectors with screws. The pin assignment of the ports is described in the technical specifications.
  • Page 52 Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO Requirements Cross-head screwdriver, size 2 Procedure ① Cover ② Screws on the cover ③ Plugs ④ Cable inlet Proceed as follows: 1. Unscrew the six screws approximately 1 cm out of the cover. The cover is designed in such a way that the screws cannot fall out.
  • Page 53: Mobile Panel 277 Ro Ports

    Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO Notes for closing NOTICE Permissible torque The connection box housing is made of plastic. Therefore, the mounting hole threads cannot handle the same amount of stress as a comparable metallic housing. Only tighten the screws with the permitted torque of 0.4 to 0.5 Nm.
  • Page 54 Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO ① Slot for a memory card ② RJ45 socket for connecting cable PN ③ Post connector, 12-pole for the connecting cable PN ④ USB socket ⑤ RS 485 port (IF 2) ⑥...
  • Page 55 Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO USB socket The USB socket is built as a sealing plug. You can deploy the USB socket in either of the two cable inlets. ① USB socket ② ③ Cable inlet NOTICE Degree of protection not fulfilled Degree of protection IP65 is only ensured if the cap on the USB socket is plugged and...
  • Page 56: Connecting A Pc

    Mounting and connecting 4.5 Connecting the Mobile Panel 277 RO 4.5.4 Connecting a PC When you update the operating system on the HMI device or want to reset the HMI device to factory settings, you have the transfer the image once again to the HMI device. To do this, connect a PC to the HMI device and then start to transfer the image using ProSave.
  • Page 57: Switching On And Testing The Hmi Device

    Mounting and connecting 4.6 Switching on and testing the HMI device Switching on and testing the HMI device Procedure Proceed as follows: 1. Switch on the power supply. The display lights up after power is switched on. A progress bar is displayed during startup.
  • Page 58 Mounting and connecting 4.6 Switching on and testing the HMI device Switching off the HMI device Quit the RemoteOperate Client software by pressing the button before switching off the HMI device. You have the following options for switching off an HMI device with no rechargeable battery: ●...
  • Page 59: Operator Controls And Displays

    Operator controls and displays Operator controls and displays on the Mobile Panel 277 RO 5.1.1 Overview ① STOP button ② Display with touch screen STOP button The STOP button allows a safety-related stop of the system being monitored, for example the triggering of the emergency stop function.
  • Page 60: Enabling Button

    Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO Standard input unit The standard input unit on the HMI device is the touch screen. All operating elements required for touch operation are displayed on the touch screen once the HMI device has started.
  • Page 61 Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO Circuit diagram The figure below shows the operating positions and interconnections of the enabling button. Switch settings The primary function of the evaluating logic is to recognize the three switch settings: Switch setting Functions Enabling button...
  • Page 62: Stop Button

    Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO The following figure shows the switching sequence during panic usage. If the operator has pressed the enabling button through to the "Panic" setting, the "Enable" setting will be skipped when the switch is released.
  • Page 63 Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO Possible application areas for the STOP button: ● The STOP button can be used to initiate a process-cycle-specific rapid stop of a monitored system (plant, machine or machine zone). The Stop operation can occur with or without a power shutdown.
  • Page 64: Safety Functions Of The Stop Button

    Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO Operation The STOP button is operated by pressing the button. Once the stop operation has been initiated, the STOP button remains engaged in the stop position. Note The STOP button engages compulsorily when activated! Releasing the STOP button...
  • Page 65 Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO In the connection box Plus, the signals of the Stop or Emergency Stop circuit are routed via the STOP button. If the Mobile Panel 277 RO is not connected, the Stop or Emergency Stop circuit of the system being monitored remains closed.
  • Page 66: Stop Button On The Connection Box Plus

    Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO 5.1.3.3 STOP button on the connection box Plus Overview The "Stop loop" function is implemented on the connection box PN Plus. The double-circuit loop is provided by four relays mounted on the printed-circuit board. ①...
  • Page 67: Using Memory Cards

    Operator controls and displays 5.1 Operator controls and displays on the Mobile Panel 277 RO 5.1.4 Using memory cards Requirements The terminal compartment of the Mobile Panel 277 RO is open. ① Slot ② Memory card symbol ③ Velcro strip for fastening the memory card Procedure for inserting a memory card Proceed as follows: 1.
  • Page 68: Changing The Touch Pen

    Operator controls and displays 5.2 Changing the touch pen Changing the touch pen Requirements You need the following tool to replace the touch pen: ● Phillips screwdriver, size 2 Procedure Proceed as follows to replace the touch pen: 1. Close the RemoteOperate Client software. 2.
  • Page 69: Holding The Mobile Panel And Fixing It To The Wall

    Operator controls and displays 5.3 Holding the mobile panel and fixing it to the wall ② 7. Place the impact guard once again on the front of the HMI device. 8. Fasten the impact guard to the back of the HMI device with screws. Result You have replaced the touch pen.
  • Page 70 Operator controls and displays 5.3 Holding the mobile panel and fixing it to the wall Fixing the Mobile Panel in position A wall-mounting bracket is available for securely fixing the HMI device in position. The Mobile Panel can be used as a stationary HMI device when it is hooked into the wall - mounting bracket.
  • Page 71: Displays On The Connection Box Pn

    Operator controls and displays 5.4 Displays on the connection box PN Displays on the connection box PN Introduction On the front of the connection box PN Plus there are six LEDs which indicate the communication status. ① LED display ② There is an "LNK"...
  • Page 72 Operator controls and displays 5.4 Displays on the connection box PN Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 73: Configuring The Operating System

    Configuring the operating system Loader Loader The following figure shows the Loader. The Loader buttons have the following functions: ● Press the "Transfer" button to set the HMI device to "Transfer" mode. The transfer mode can only be activated when at least one data channel has been enabled for the transfer.
  • Page 74 Configuring the operating system 6.1 Loader ● Press the "Taskbar" button to activate the taskbar with the Windows CE start menu open: Open Loader The following options are available to open the Loader: ● The Loader appears briefly after starting the HMI device ●...
  • Page 75: Control Panel

    Configuring the operating system 6.2 Control Panel Control Panel 6.2.1 Overview Control Panel of the HMI device The following settings, for example, can be made in the Control Panel of the HMI device: ● Password protection for the HMI device ●...
  • Page 76: Reference

    Configuring the operating system 6.2 Control Panel 6.2.2 Reference Overview of functions The following table shows the settings in the Control Panel. Some settings are only effective when a project is running on the HMI device. These settings are not relevant for the Mobile Panel 277 RO and are marked accordingly in the table below. Icon Functions Tab / entry...
  • Page 77: Operating The Control Panel

    Configuring the operating system 6.2 Control Panel Icon Functions Tab / entry Changing the PROFINET IO setting – Changing regional settings – Not relevant for the Mobile Panel 277 RO. Changing S7 transfer settings – Not relevant for the Mobile Panel 277 RO. Setting the screen saver –...
  • Page 78 Configuring the operating system 6.2 Control Panel 6. Confirm the selection with the button or abort the entry with the button. The dialog closes. 7. Close the Control Panel with the button. 8. Start the RemoteOperate Client application by pressing "Start" in the loader. Input with the screen keyboard A screen keyboard is available for data input.
  • Page 79: Changing Settings For Operation

    Configuring the screen keyboard Introduction You can change the layout and the position of the screen keyboard as follows. Requirements You have opened the "Siemens HMI InputPanel - Options" dialog with the "InputPanel" icon. ① Button for displaying the screen keyboard ②...
  • Page 80: Setting The Character Repeat Rate Of The Screen Keyboard

    Configuring the operating system 6.3 Changing settings for operation Procedure Proceed as follows: 1. Press the "Open Input Panel" button to display the screen keyboard. 2. By pressing the button, you can switch between the numerical and alphanumerical screen keyboard. 3.
  • Page 81: Setting The Double-Click

    Configuring the operating system 6.3 Changing settings for operation Procedure Proceed as follows: 1. Activate the "Enable character repeat" check box to enable the character repeat. 2. Use the buttons to set the delay and rate of the character repeat. You can also use the slider control for this.
  • Page 82: Calibrating The Touch Screen

    Configuring the operating system 6.3 Changing settings for operation Procedure Proceed as follows: 1. Double-click the pattern twice. After one double-click the pattern is shown in inverse colors. 2. Double-click the symbol twice. If the double-click is valid, the icon is displayed as follows: 3.
  • Page 83 Configuring the operating system 6.3 Changing settings for operation Procedure Proceed as follows: 1. Touch the "Recalibrate" button to open the following dialog: ① 2. Briefly touch the middle of the calibration crosshairs The calibration crosshairs is then displayed at four more positions. Touch the middle of the calibration crosshairs for each position.
  • Page 84: Changing Password Protection

    Configuring the operating system 6.4 Changing password protection Changing password protection Introduction You can protect the Control Panel and Windows CE taskbar with a password. Requirements You have opened the "Password Properties" dialog box by touching the "Password" icon. ① Password text box ②...
  • Page 85: Changing Hmi Device Settings

    Configuring the operating system 6.5 Changing HMI device settings Procedure for deactivating password protection Proceed as follows: 1. Delete the entries in the "Password" and "Confirm password" text boxes. 2. Confirm your entries. The dialog closes. Result Password protection for the Control Panel and Windows CE taskbar is disabled. Changing HMI device settings 6.5.1 Setting the date and time...
  • Page 86 Configuring the operating system 6.5 Changing HMI device settings Procedure Proceed as follows: 1. Select the appropriate time zone for the HMI device from the "Time Zone" selection field. 2. Touch the "Apply" button to confirm your entry. The time of day shown in the "Current Time" field is adjusted correspondingly to the selected time zone.
  • Page 87: Backup Registry Information

    Configuring the operating system 6.5 Changing HMI device settings 6.5.2 Backup registry information Registry information and temporary data You can install and uninstall your own programs on the HMI devices under Windows CE. You must save the registry settings after installation or uninstallation. You can save the following data to the flash memory: ●...
  • Page 88: Changing Monitor Settings

    Configuring the operating system 6.5 Changing HMI device settings Procedure Proceed as follows: 1. Select the "Save Registry" button to save the current registry settings. 2. Select the "Save Files" button to save temporary files. 3. Specify how the file system on the memory card should be restored. –...
  • Page 89: Setting The Screen Saver

    Configuring the operating system 6.5 Changing HMI device settings Procedure Proceed as follows: 1. You can increase the brightness of the screen by pressing the "UP" button. Alternatively, you can reduce the brightness of the screen with the "DOWN" button. 2.
  • Page 90 Configuring the operating system 6.5 Changing HMI device settings Requirements You have opened the "Screensaver" dialog with the "ScreenSaver" icon. ① Time interval in minutes until backlighting is reduced ② Period of time in minutes before the screen saver is activated ③...
  • Page 91: Restarting The Hmi Device

    Configuring the operating system 6.5 Changing HMI device settings 6.5.5 Restarting the HMI device Introduction You need to reboot the HMI device if you have changed the setting for the time zone. CAUTION Data loss when the HMI device is restarted All volatile data is lost when the HMI device is rebooted.
  • Page 92: Displaying Information About The Hmi Device

    Configuring the operating system 6.5 Changing HMI device settings 6.5.6 Displaying information about the HMI device Introduction You will need the device-specific information if you contact A&D Technical Support. Requirements You have opened the "OP Properties" dialog box, "Device" tab, by touching the "OP" icon.
  • Page 93: Displaying System Properties

    Configuring the operating system 6.5 Changing HMI device settings 6.5.7 Displaying system properties Introduction The system-specific information provides you with information about the processor, operating system and memory of the HMI device. Requirements You have opened the "System Properties" dialog with the "System" icon.
  • Page 94 Configuring the operating system 6.5 Changing HMI device settings Procedure for displaying memory information Note "Memory" tab Do not change the memory distribution in the "Memory" tab. Only applies for the usage of options: An alteration to the memory distribution may be necessary. Please refer to the accompanying documentation for further information.
  • Page 95: Setting The Delay Time

    Configuring the operating system 6.6 Setting the delay time Setting the delay time Introduction After switching on the HMI device, the RemoteOperate Client application starts after a delay time. The Loader is displayed during the delay time. Requirements You have opened the "Transfer Settings" dialog box, "Directories" tab, by touching the "Transfer"...
  • Page 96: Communication Settings

    Configuring the operating system 6.7 Communication settings Communication settings 6.7.1 Configuring the data channel Introduction If you disable all data channels, the HMI device is protected against unintentional overwriting of the HMI device image. Note An image can only be transferred from a PC to the HMI device if at least one of the data channels is enabled on the HMI device.
  • Page 97 Configuring the operating system 6.7 Communication settings Procedure Proceed as follows: 1. You can enable the required data channel by activating the corresponding "Enable Channel" check box in the "Channel 1" or "Channel 2" group. In the "Channel 1" group, the RS-422/RS-485 port is enabled for the serial data transfer. –...
  • Page 98: Checking The Profinet Io Settings

    Configuring the operating system 6.7 Communication settings General information Note Changes during the "Transfer" operating mode If the HMI device is in "Transfer" mode while changes are made to the transfer settings, the settings only go into effect after the transfer function is restarted. This may occur if the Control Panel is opened to change the transfer properties during the process control phase.
  • Page 99: Configuring Network Operation

    Configuring the operating system 6.8 Configuring network operation Configuring network operation 6.8.1 Setting the device name of the HMI device Introduction The HMI device uses the device name to identify itself in the network. Requirements You have opened the "System Properties" dialog with the "System" icon.
  • Page 100: Changing The Network Configuration

    Configuring the operating system 6.8 Configuring network operation 6.8.2 Changing the network configuration Overview You can change the network settings for the LAN connection under "Network & Dial-Up Connections". Requirement - changing LAN connection settings You have opened the following display by touching the "Network&Dial-Up Connections" icon.
  • Page 101: Changing The Logon Data

    Configuring the operating system 6.8 Configuring network operation 4. If a name server is used in the network, change to the "Name Server" tab. 5. Enter the respective addresses in the text boxes. 6. Confirm your entries. The dialog closes. 7.
  • Page 102: Backup And Restore With The Memory Card

    Configuring the operating system 6.9 Backup and restore with the memory card Procedure Proceed as follows: 1. Enter the user name in the "User name" text box. 2. Enter your password in the "Password" text box. 3. Enter the domain name in the "Domain" text box. 4.
  • Page 103 Configuring the operating system 6.9 Backup and restore with the memory card Procedure Proceed as follows: 1. Select "BACKUP" to start Backup. 2. The HMI device checks the memory card. If no memory card is inserted in the card slot of the HMI device or if the memory card is damaged: –...
  • Page 104: Restore From The Memory Card

    Configuring the operating system 6.9 Backup and restore with the memory card 6.9.2 Restore from the memory card Introduction A restore operation deletes the old data from flash memory of the HMI device on confirmation. The data stored on the memory card is then copied to the internal flash memory.
  • Page 105 Configuring the operating system 6.9 Backup and restore with the memory card 3. The data to be restored is checked. The following messages are displayed in sequence during the check: – "Starting Restore" – "Checking data". 4. When the data has been checked, the following prompt for confirmation is displayed: "You are starting RESTORE now.
  • Page 106: Display Rechargeable Battery Charge Level

    Configuring the operating system 6.10 Display rechargeable battery charge level 6.10 Display rechargeable battery charge level Introduction The rechargeable battery is an optional accessory. The "OP Properties" dialog box, "Accu" tab, displays the remaining capacity and temperature of the rechargeable battery. Requirements You have opened the "OP Properties"...
  • Page 107: Using Remoteoperate Client

    Using RemoteOperate Client Creating/editing a server selection list When you switch on the HMI device and once the HMI device starts up, the server selection list is displayed in the "Client - RemoteOperate" dialog box: Note When you switch on the HMI device for the first time, the server selection list is empty. You must first create a new server.
  • Page 108 Using RemoteOperate Client 7.1 Creating/editing a server selection list Creating a new server Note Limited number of servers per client RemoteOperate supports a maximum of ten servers in a client's server selection list. If you wish to create a new server, make sure that there are no more than nine servers in the server selection list.
  • Page 109 Using RemoteOperate Client 7.1 Creating/editing a server selection list Note The path of the server selection list has a maximum of three levels. Specify no more than three path levels for a server, for example "\Area2\Segment1\Place2\". If the path already exists in the server selection list, the new server will be inserted at this point.
  • Page 110: Connecting A Client

    Using RemoteOperate Client 7.2 Connecting a client Connecting a client Requirement ● You have switched on the HMI device. Note If you have switched on the HMI device for the first time, the server selection list is empty. Create a new server selection list. Procedure 1.
  • Page 111 Using RemoteOperate Client 7.2 Connecting a client 2. Connect the client to the selected server using the button. While the client is trying to connect to the server, the following message is displayed on your HMI device: Note Response to a network fault If a transient or long-term network fault occurs, the client repeatedly tries to establish a connection to the server.
  • Page 112 Using RemoteOperate Client 7.2 Connecting a client The operator authorization window ("traffic lights") The operator authorization window, known as "traffic lights", is displayed in the foreground on the server screen and the screens of all connected clients with operator authorization. The traffic lights can assume the following states: Traffic light icon Activated by...
  • Page 113 Using RemoteOperate Client 7.2 Connecting a client The RemoteOperate toolbar If you press the touch screen for more than five seconds (time can be configured in the roServer.ini), the RemoteOperate toolbar is displayed in the foreground on your screen. Alternatively, if you have operator authorization, you can left-click the traffic light to open the RemoteOperate toolbar.
  • Page 114: Changing The Server

    Using RemoteOperate Client 7.3 Changing the server Changing the server Requirements ● The HMI device is connected as a client to a server. Procedure Proceed as follows: 1. Press the touch screen until the RemoteOperate toolbar is displayed. If you have operator authorization you can, as an alternative, click the traffic lights. Note Setting the time to display the toolbar The length of time you need to press the touch screen before the RemoteOperate toolbar...
  • Page 115: Start Client

    Using RemoteOperate Client 7.4 Start client Start client The RemoteOperate Client can be optionally started with the following parameters: [Autostart] roClient.exe \server=0 RemoteOperate Server IP address or index (start- ing with 0) of the server selection dialog (SIMATIC IPC only) roClient.exe \ip=192.168.56.2 RemoteOperate Server IP address roClient.exe \timeout=600...
  • Page 116 Using RemoteOperate Client 7.5 Closing the RemoteOperate Client 2. Close the connection to the server using the button. The server selection list is displayed: Close the RemoteOperate Client software using the button in the upper right corner of the window. Note Password protection If your HMI device is password protected, you are prompted for the password at this point.
  • Page 117: Example: Assigning Operator Authorization

    Using RemoteOperate Client 7.6 Example: Assigning operator authorization The loader contains the following four buttons: ● Use the "Transfer" button to transfer data from a PC to the HMI device. ● Use the "Start" button to open the server selection list. ●...
  • Page 118 Using RemoteOperate Client 7.6 Example: Assigning operator authorization Sequence of the example scenario During the operation of a plant control system, the request, refusal and transfer of operator authorizations could look like this: Client 1, client 2, and client 3 are entered in the list of "available clients" on the server. All clients are granted the right to connect to the server and to operate on the server.
  • Page 119 Using RemoteOperate Client 7.6 Example: Assigning operator authorization ● The user on client 1 touches the green traffic light twice in quick succession (double-click) and gives up exclusive operator authorization. Client 1 continues to operate. The traffic light for client 1 turns green. The traffic lights for client 2, client 3, and the server turn red: Client 1 Client 2...
  • Page 120 Using RemoteOperate Client 7.6 Example: Assigning operator authorization ● The operator at client 1 enables the "Forced Exclusive" mode, for example with a switch close to the HMI device. The traffic light of client 1 turns completely green and all other traffic lights turn completely red.
  • Page 121: Backing Up And Restoring Data

    Backing up and restoring data Requirements ● The HMI device is connected to a PC by means of the connection box and Ethernet. ● The ProSave application is installed on the PC. The ProSave software is located on the "SIMATIC RemoteOperate - Applications & Documentation" CD. ●...
  • Page 122 Backing up and restoring data Procedure for restoring Proceed as follows: 1. Start ProSave from the Windows Start menu on the PC. 2. Select the HMI device type "Mobile Panel 277 RO" in the "General" tab. 3. Select "Ethernet" as the connection type between the HMI device and the PC. 4.
  • Page 123: Maintenance And Care

    Maintenance and care Maintenance and care Scope of maintenance The HMI device is designed for maintenance-free operation. You should clean the touch screen at regular intervals, however. CAUTION Inadvertent operation Always switch off the HMI device before cleaning it. This will ensure that you do not trigger functions unintentionally when you touch the keys.
  • Page 124: Update Hmi Device Image

    Maintenance and care 9.2 Update HMI device image Update HMI device image The following applications are pre-installed on the HMI device: ● The Microsoft Windows CE 5.0 operating system ● The RemoteOperate Client software The operating system and the RemoteOperate Client software are located in an image on the "SIMATIC RemoteOperate - Applications &...
  • Page 125: Spare Parts And Repairs

    The Mobile Panel 277 RO HMI device is covered by the conditions of repair and return of equipment, as follows: 1. You return the defective device to the A&D returned goods center. The address is: Siemens AG Industry Sector Returns Center Siemensstr.
  • Page 126 Maintenance and care 9.3 Spare parts and repairs Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 127: Technical Specifications

    Technical specifications 10.1 Dimension drawings 10.1.1 Mobile Panel 277 RO Front view Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 128 Technical specifications 10.1 Dimension drawings Side view Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 129: Wall-Mounting Bracket

    Technical specifications 10.1 Dimension drawings 10.1.2 Wall-mounting bracket Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 130: Connection Box Pn Plus

    Technical specifications 10.1 Dimension drawings 10.1.3 Connection box PN Plus Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 131: Specifications

    Technical specifications 10.2 Specifications 10.2 Specifications 10.2.1 Mobile Panel 277 RO HMI device Weight without packing Approx. 2.3 kg Display Type Color TFT-LC Display Display area, active (W x H) 211.2 mm x 158.4 mm (10") Resolution 800 x 600 pixels Colors, displayable 64k colors Brightness control...
  • Page 132: Rechargeable Buffer Battery

    Technical specifications 10.2 Specifications Ports 1 x RS 485 Max. 12 Mbit/s 1 x USB USB host; conforms to USB standard 1.1 (supporting low- • speed and full-speed USB devices) Maximum load 500 mA • 1 x RS 45 For Ethernet 1 x plug-in terminal strips (12-pin) For Ethernet Supply voltage...
  • Page 133: Safety Characteristics

    Technical specifications 10.2 Specifications 10.2.3 Safety characteristics Note The fail-safe performance characteristics in the technical data apply to a proof-test interval of 20 years. STOP button Rated voltage 24 V DC Minimum current 10 mA, per contact Max. current carrying capacity 500 mA, per contact Utilization category DC-13, in accordance with IEC 60947-5-1...
  • Page 134: Connection Box Pn Plus

    Technical specifications 10.2 Specifications 10.2.4 Connection box PN Plus Weight Weight without packing Approx. 700 g Supply voltage Rated voltage +24 VDC Permitted voltage range 20.4 V to 28.8 V (–15 %, +20 %) Transients, maximum permissible 35 V (500 ms) Time between two transients, minimum 50 s Power consumption connection...
  • Page 135: Mobile Panel 277 Ro Interface Assignment

    Technical specifications 10.3 Mobile Panel 277 RO interface assignment 10.3 Mobile Panel 277 RO interface assignment 10.3.1 RS 485 (IF 2) Sub-D socket, 9-pin, with screw lock Assignment n. c. GND 24 V Data channel B (+) n. c. GND 5 V, floating +5 VDC, floating +24 VDC, out (max.
  • Page 136: Rj45 For Connecting Cable Pn

    Technical specifications 10.3 Mobile Panel 277 RO interface assignment 10.3.3 RJ45 for connecting cable PN RJ45 plug connector, 8-pin Assignment TD– n. c. n. c. RD– ICD+ ICD– 10.3.4 Post connector for connecting cable PN Post connector, 12-pin Assignment Circuit +24 VDC Power supply GND 24 V...
  • Page 137: Connection Box Pn Plus Interface Assignment

    Technical specifications 10.4 Connection box PN Plus interface assignment 10.4 Connection box PN Plus interface assignment Position of the ports ① Fast connector ② Terminal strip 1 ③ Terminal strip 2 Fast connector, 4-pin The connection box contains two fast connectors for connecting the PROFINET data cables. The figure below illustrates the assignment of the fast connector: Color Assignment connection box...
  • Page 138 Technical specifications 10.4 Connection box PN Plus interface assignment Terminal strip 1, for power supply, 3-pin The figure below illustrates the assignment of terminal strip 1: Assignment Terminal strip 2, 12-pin The safety and additional functions are connected to this terminal strip. The terminal strip has a mechanical coding to prevent it from being mixed up with terminal strip 1.
  • Page 139 Technical specifications 10.4 Connection box PN Plus interface assignment Typical circuit diagrams for connection box Plus Typical circuit diagram: Mobile Panel 277 RO not connected and power supply switched on: Typical circuit diagram: Mobile Panel 277 RO connected, power supply switched on and Emergency Stop inactive: Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 140 Technical specifications 10.4 Connection box PN Plus interface assignment Typical circuit diagram: Mobile Panel 277 RO connected, power supply switched on and Emergency Stop active: Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 141 Technical specifications 10.4 Connection box PN Plus interface assignment Typical circuit diagram: Power supply switched off Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 142: Wiring Examples For Enabling Switch And Stop Button

    Technical specifications 10.5 Wiring Examples for Enabling Switch and STOP Button 10.5 Wiring Examples for Enabling Switch and STOP Button Introduction This chapter contains connection examples for enabling and STOP buttons corresponding to Category 3 PL d in accordance with EN ISO 13849-1:2008/AC:2009. Note To ensure Category 3 PL d in accordance with EN ISO 13849-1:2008/AC:2009, be sure to follow the operating instructions for the monitoring device being used.
  • Page 143 Technical specifications 10.5 Wiring Examples for Enabling Switch and STOP Button Connection example 1 – Enabling button with safety circuit device The following figure shows the connection of a SIRIUS 3TK2841 safety circuit device to the enabling button of the mobile panel. All contacts of the safety relay (contactor) KA and KB are fitted with positively-driven contacts in accordance with EN 50205:2002.
  • Page 144 Technical specifications 10.5 Wiring Examples for Enabling Switch and STOP Button Connection example 2 – STOP button with safety circuit device The following figure shows the connection of a SIRIUS 3TK2822 or SIRIUS 3TK2841 to the STOP button of the mobile panel. All contacts of the safety relay (contactor) KA and KB are fitted with positively-driven contacts in accordance with EN 50205:2002.
  • Page 145: Appendix

    You can find additional information and support for the products described on the Internet at the following addresses: ● Technical support (https://support.industry.siemens.com) ● Support request form (http://www.siemens.com/automation/support-request) ● After Sales Information System SIMATIC IPC/PG (http://www.siemens.com/asis) ● SIMATIC Documentation Collection (http://www.siemens.com/simatic-tech-doku-portal) ● Your local representative (http://www.automation.siemens.com/mcms/aspa-db/en/Pages/default.aspx) ●...
  • Page 146: Esd Guideline

    Appendix A.2 ESD guideline ESD guideline Definition of ESD All electronic modules are equipped with large-scale integrated ICs or components. Due to their design, these electronic elements are highly sensitive to overvoltage, and thus to any electrostatic discharge. These electronic components are therefore specially identified as ESDs.
  • Page 147 Appendix A.2 ESD guideline Electrostatic charging NOTICE Electrostatic charging ESDs may be destroyed by voltages far below the level perceived by human beings. Voltages of this kind develop when a component or an assembly is touched by a person who is not grounded against static electricity. Usually, it is unlikely that damage to an ESD as a result of overvoltage is detected immediately but may become apparent only after a longer period of operation.
  • Page 148 Appendix A.2 ESD guideline Protective measures against electrostatic discharge NOTICE Observe grounding measures When working with electrostatic sensitive devices, make sure that the person, the workplace and the packaging are properly grounded. This helps to avoid electrostatic charging. As a rule, only touch the ESD if this is unavoidable, for example for maintenance. When you touch modules, make sure that you do not touch the pins on the modules or the PCB tracks.
  • Page 149: Abbreviations

    Abbreviations Abbreviations Direct Current DHCP Dynamic Host Configuration Protocol Domain Name System Components and modules endangered by electrostatic discharge Electromagnetic Compatibility European standard Components and modules endangered by electrostatic discharge Ground High Frequency Human Machine Interface International Electronic Commission Interface Internet Protocol Light Emitting Diode Media Access Control...
  • Page 150 Abbreviations B.1 Abbreviations Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...
  • Page 151: Glossary

    Glossary Automation system Controller of the SIMATIC S7 series such as a SIMATIC S7-300 Bootloader Used to start the operating system. Automatically started when the HMI device is switched on. After the operating system has been loaded, the Loader opens. Electromagnetic compatibility is the ability of electrical equipment to function properly in its electromagnetic environment without influencing this environment.
  • Page 152 Glossary Plant General term referring to machines, processing centers, systems, plants and processes which are operated and monitored on an HMI device. A PLC is a general term for devices and systems with which the HMI device communicates, e.g. SIMATIC S7. Project Result of a configuration using a configuration software.
  • Page 153: Index

    Index Editing server properties, 109 Reboot, 92 Recalibrate, 82 Remove server, 109 Abbreviations, 149 RESTORE, 102, 104 Accessories Right-click, 113 Accessory kit, 11 Save, 79 Accessory kit, 11 Save Files, 87 Activate Save Registry, 87 Password protection, 84 Screen keyboard, 113 Address assignment Start, 73 TCP/IP network, 100...
  • Page 154 Index Clearance Connection example, 142 Connection box, 36 Enabling button, 143 Wall-mounting bracket, 36 Safety circuit device, 144 Client STOP button, 144 Closing, 115 with category 3 PL d, 142, 143, 144 Connect to a new server, 114 Connection graphic Connect to a server, 110 Equipotential bonding, 46 Definition, 4...
  • Page 155 Index Restarting, 76 Specifications, 131 EC Declaration of Conformity, 22 Switch off, 58 Editing HMI Input Panel Server properties, 109 Options, 79 Server selection list, 107 Electrical Installation, 41 Electrical potential difference, 45 Identification, 101 Electrostatic charging, 147 IF1 port Electrostatic discharge Assignment, 138 Precautions, 148...
  • Page 156 Index Network & dial-up connections, 76 Network fault, 111 MAC address, 92 Network ID, 76 Maintenance, 123 Network operation Mechanical Device name, 99 Storage conditions, 31 Transport conditions, 31 Memory OP properties, 76 Specifications, 131 Device, 92 Memory card Persistent storage, 87 Backup to, 102 Touch, 82 Inserting, 67...
  • Page 157 Index Ports, 53 Risk from improper use Mobile Panel 277, 132 Enabling button, 27 Power failure, 134 RJ45 socket Power supply Safety instruction, 54 Cable cross-section, 48 Connection graphic, 48 Precautions Safe electrical separation, 48 Electrostatic discharge, 148 Safety PROFINET IO Standards, 23, 25 Setting, 77 Safety characteristics, 133...
  • Page 158 Taskbar button, 117 Time, 85 TCP/IP address, 100 SIBE Switzerland Certification Service, 22 Temporary files Backup, 87 Side view, 10, 128 Siemens HMI input panel options, 76 Test Special operation For ambient conditions, 34 Testing Risk assessment, 26 Specifications Mobile Panel, 57...
  • Page 159 Index Traffic lights, 112 Transfer button, 117 Transfer settings, 77, 96 Channel, 96 Directories, 95 Transport conditions, 31 Transport damage, 39 Tree path input box, 108 Typical circuit diagram Connection box, 139 UL approval, 22 Usage Conditions, 33 In industry, 24 In residential areas, 24 Mobile Panel, 9 With additional measures, 33...
  • Page 160 Index Mobile Panel 277 RO Operating Instructions, 10/2015, A5E36824256-AA...

Table of Contents