Maintenance Set Up Group

The Maintenance set up group consists of information about actuator operation accumulated through time.
This information (or maintenance statistics) can be used to evaluate actuator operation and determine
predicted or scheduled maintenance periods. Table 22 lists the parameters and selections available for the
SET MAINTENANCE group.
Please note that maintenance statistics are written to the EEPROM every 8 hours. Therefore the statistics
are saved in the event of a power interruption.
Actuator Lower
Display
Prompt
TEMP
TEMPHI
TEMPLO
hh:mm:ss †
STARTS
RLnCNT
n = 1, 2, 3 or 4
REGNn
n = 0 to 9
TOTDEG
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/08

Table 22 Maintenance Set Up Group Parameters

Selections or
PDA users: The prompts are organized differently on your PDA's
Range of Setting
software. Grayed prompts are under Configuration, Maintenance. Non-grayed
ACTUATOR TEMPERATURE — Read Only. Displays the
nnnn F *
current internal temperature of the actuator.
HIGH TEMPERATURE LIMIT — Displays the high
nnnn F *
temperature limit of the internal actuator temperature since it
was last reset.
LOW TEMPERATURE LIMIT — Displays the low
nnnn F *
temperature limit of the internal actuator temperature since it
was last reset.
ACST †
ACCUMULATED STALL TIME — Displays the accumulated
stall time of the actuator motor since it was last reset.
ACCUMULATED MOTOR STARTS — Displays the
nnnn
accumulated motor starts since it was last reset. Multiply
displayed value times 10
999,900,000.
RELAY CYCLE COUNTS — Displays the accumulated cycle
nnnn
counts of a relay since it was last reset. One relay cycle is
when a relay is energized and deenergized. Multiply
displayed value times 10
999,900,000.
ACCUMULATED MOTOR STARTS — Displays the
nnnn
accumulated motor starts in the 1
it was last reset. See
Regions of Motor Travel (page 62). Multiply displayed value
times 10
TOTAL DEGREES OF MOTOR TRAVEL — Displays the
nnnn
total number of degrees of motor travel since it was last
reset. Multiply displayed value times 10
Range is 0 to 999,900,000.
Set Up and Calibration Procedures
Parameter Definition/PDA HercuLink
prompts are under Maintenance.
5
to get actual value. Range is 0 to
5
to get actual value. Range is 0 to
5
to get actual value. Range is 0 to 999,900,000.
Maintenance Set Up Group
®
Prompt
HercuLink
st
10% of motor span since
5
to get actual value.
®