Set Up and Calibration Procedures
Drive Set Up Group
Set Tag Name
The actuator tag name can be an alphanumeric name up to six characters. The tag name is set by using the
keys on the keypad and the local display. Follow the steps below to set the tag name.
Step
Press SET UP key until the display reads SET DRVINF.
1
Press the FUNCTION key until the upper display reads TAG.
2
The lower display contains six digits. A decimal point will be flashing at the leftmost digit for
3
approximately three seconds. Then the decimal point shifts to the right and flashes for three
seconds before shifting again to the right. This pattern repeats continuously.
4
Set the digit to the left of the flashing decimal point. Use the
the character set of 0 through 9, the letters 'a' through 'z' and the letters 'A' through 'Z' . Scroll
through until the desired character is displayed.
5
Wait for the decimal point to shift to the right and then scroll through using the
until the next character is displayed.
Repeat for each character of the tag until the complete tag name is displayed.
6
Press the FUNCTION key to go to the next parameter, or press DISPLAY to exit set up mode.
7
58
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Action
or
keys to scroll through
or
keys
Revision 7
7/08