Table 26 Motor Calibration Procedure - Honeywell HercuLine 2000 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for HercuLine 2000 Series:
Table of Contents

Advertisement

Set Up and Calibration Procedures
Calibration
Calibrate Motor
Use the procedure in Table 26 to calibrate the actuator motor for 0% and 100% input signal
ATTENTION
For a motor calibration to be saved, you must complete the procedure. The calibration will not
be saved if you exit without completing the steps of the procedure.
ATTENTION
When calibrating the motor to a short stroke range, you must reset the end-of-travel limit
switches. See Setting End-of-Travel Limit Switches.
Step
Operation
Enter Calibration
1
Mode
Calibrate Zero (0%)
2
Calibrate Span
3
(100%)
4
70
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Table 26 Motor Calibration Procedure

Press
SETUP
Upper Display =
until you see
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Upper Display =
or
key
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its low position.
Wait 5 seconds, then go to step 3.
FUNCTION
Upper Display =
Lower Display =
Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its high position.
Wait 5 seconds, then go to step 4.
FUNCTION
Calibration for zero and span motor positions are now saved.
Motor calibration is complete.
NOTE: The display will automatically go to the CAL CURENT
set up display. See Table 27. You may also exit calibation
mode by pressing the DISPLAY or SETUP keys.
Result
CAL
MOTOR
DIS
CALMTR
BEGN
CALMTR
APLY
MTR LO
APLY
MTR HI
Revision 7
7/08