Burner Control/Flame Safety
Master/Slave Arrangement
Split Valve Configuration
A common heat or cool type process requires two valves. In this case the controller has only one output.
The two motor positioners are calibrated differently, one responds to 4 to 12mA and the other responds
to 12 to 20mA. At 12mA, both valves are closed; one opening below 12mA and the other above 12mA.
Refer to Figure 20 for an interconnection diagram for split valve operation using two actuators.
Current Output Controller
Note: Controller must
be capable of sourcing
the impedance.
Preferred
Wiring
NOTE: If using HART
Current Output Controller
Alternate
Wiring
NOTE: If using HART
30
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
+
4 to 20 mA
-
®
communications, for this application HART
+
4 to 20 mA
-
See Figure
27 for jumper
location

Figure 20 Interconnection Diagrams

®
communications, for this application HART
10260S Series Actuator #1
Actuator #1
Hot
Jumper W2
Neutral
= Current
250 Ohms
Ground
1 to 5 VDC
Actuator #2
10260S Series Actuator #2
Jumper W2
Hot
= Current
Neutral
250 Ohms
Ground
1 to 5 VDC
®
must be configured for Multi-drop operation.
Actuator #1
10260S Series Actuator #1
Jumper W2
Hot
= Current
Neutral
250 Ohms
Ground
1 to 5 VDC
Actuator #2
10260S Series Actuator #2
Jumper W2
Hot
= Voltage
Neutral
Ground
®
must be configured for Multi-drop operation.
120/240
VAC
See Figure
27 for jumper
location
120/240
VAC
120/240
VAC
120/240
VAC
Revision 7
7/08