GE MultiLink ML1200 Instruction Manual page 88

Managed field switch
Hide thumbs Also See for MultiLink ML1200:
Table of Contents

Advertisement

IP ADDRESSING
[SYSTEM]
***Edit below this line only***
system_name=ML1200
system_contact=support@gemultilin.com
system_location= Markham, Ontario
boot_mode=manual
system_ip=192.168.5.5
system_subnet=0.0.0.0
system_gateway=0.0.0.0
idle_timeout=10
telnet_access=enable
snmp_access=enable
web_access=enable
***Edit above this line only***
##########################################################
# User Accounts - This area configures user accounts for #
#
##########################################################
...
Note
5–16
accessing this system.
1.
A config file allows only certain portions of the file to be edited by a user. Changing
any other part of the file will result in the system not allowing the file to be loaded, as
the CRC computed and stored in the file would not be matched. Should you want to
edit, edit the System portion of the file only. GE Multilin, Inc. recommends editing the
"script" file (see below)
2.
File names cannot have special characters such as *#!@$^&* space and control
characters.
#
FIGURE 5–1: Contents of a config file
MULTILINK ML1200 MANAGED FIELD SWITCH – INSTRUCTION MANUAL
CHAPTER 5: IP ADDRESSING