5 | Assembly
5.4 Minimum installation distances
5.5 Mounting of the control
28
Fig. 12: Installation distances
Dimension
A
B
C
D
E
1)
F
1) Distance to upstream control elements in the control cabinet door.
The control is designed for mounting on a mounting rail. The mounting rail is part of the
EMC concept and is therefore mandatory. Requirements on the mounting rail:
• The mounting rail must be made of conductive metal.
• Permissible types are TH35/7,5 and TH35/15 in accordance with
• The mounting rail serves as functional earth and must be mounted on a metallic,
earthed place (e.g. rear wall of the control cabinet). If this is not possible, the mounting
rail must be connected to the functional equipotential bonding via separate connection.
The conductor should have a cross section of at least 4 mm².
• To prevent vibration problems, the mounting rail should be connected to the mounting
bracket maximally every 200 mm.
• Ensure that there is no heat build-up in a multi-level structure.