Wiring Control Circuit Terminals

Wire Sizes

For remote operation using analog signals, the control line length between the Analog Operator or operation
signals and the Inverter should be less than 30 m. The controller wires should always be separated from main
power lines or other control circuits in order to avoid disturbances.
It is recommended to use shielded twisted-pair wires and ground the shield for the largest area of contact
between shield and ground.
The terminal numbers and the appropriate wire sizes are shown in
Table 2.7 Terminal Numbers and Wire Sizes (Same for all Models)
Terminals
AC, SC, A1, +V, S1, S2, S3,
S4, S5, S6, S7, BB, MA,
MB, MC, M1, M2, M3, M4,
M5, M6
E (G)
*1. Ferrules with plastic sleeves should be used for the signal lines to simplify wiring and improve reliability.
Ferrules for Signal Lines
Models and sizes of ferrules with plastic sleeves for the signal lines are shown in the following table.
2
Wire Size mm
(AWG)
0.25 (24)
0.5 (20)
0.75 (18)
1.5 (16)
2 (14)
Possible Wire
Tightening
Terminal
Sizes
Torque
Screws
(N•m)
mm
Solid wire
0.5 to 2.5
Phoenix
0.5 to 0.6
Stranded wire:
type
0.5 to 1.5
(26 to 14)
0.5 to 2.5 (20 to
M3.5
0.8 to 1.0
Table 2.8 Ferrule Sizes
Model
d1
AI 0.25 - 8YE
0.8
AI 0.5 - 8WH
1.1
AI 0.75 - 8GY
1.3
AI 1.5 - 8BK
1.8
AI 2.5 - 8BU
2.3
Fig 2.10 Ferrule Sizes
Table
2.7.
Recom-
mended Wire
Size
2
(AWG)
2
mm
(AWG)
*1:
0.75
• Shielded, twisted-pair wire
(18)
• Shielded, polyethylene-covered,
vinyl sheath cable
1.0
(12)
14)
d2
L
2
12.5
2.5
14
2.8
14
3.4
14
4.2
14
Wire Type
Manufacturer
Phoenix Contact
17
2-
2