Wiring Control Circuit Terminals - Omron SYSDRIVE 3G3EV User Manual

Compact low-noise inverter
Hide thumbs Also See for SYSDRIVE 3G3EV:
Table of Contents

Advertisement

Design

3-2-3 Wiring Control Circuit Terminals

The control signal line must be 50 m or less and must be separated from
the power line. If frequency references are input externally, use a twisted-
pair shielded line.
H Wiring Sequence Input/Output Terminals
Wire the sequence input terminals (SF, SR, S1, and SC) and the multi-function contact
output terminals (MA, MB, and MC) as described below.
D Wires to be Used
Wire type
Single wire
Stranded wire
D Wiring Method
•Wire each terminal as follows:
a) Loosen the terminal screw with a thin-slotted screwdriver.
b) Insert the wire from underneath the terminal block.
c) Tighten the terminal screw firmly.
•Always separate the control signal line from the main circuit cables and other power
cables.
Length of
stripped portion:
Approx. 5.5 mm
H Wiring Frequency Reference Input Terminals
If frequency references are input using a D/A unit (digital-to-analog converter) or exter-
nal power supply, wire the frequency reference input terminals (FR and FC) as de-
scribed below.
Wire size
2
0.5 to 1.25 mm
2
0.5 to 0.75 mm
Thin-slotted screwdriver
Do not solder this portion.
(Otherwise, faulty contact may result.)
Wire
Wire to be used
Polyethylene-shielded cable
Control circuit
terminal block
Chapter 3
3-17