MEMOBUS Message Example
An example of MEMOBUS command/response messages is given below.
Reading Inverter Memory Register Contents
The content of maximum 16 inverter memory registers can be read out at a time.
Among other things the command message must contain the start address of the first register to read out and
the quantity of registers. The response message will contain the content of the first and the consecutive num-
ber of registers that has been set for the quantity.
The contents of the memory register are separated into higher 8 bits and lower 8 bits.
The following tables show message examples when reading status signals, error details, data link status, and
frequency references from the slave 2 Inverter.
Command Message
Slave Address
Function Code
Start Address
Quantity
CRC-16
6
Loop back Test
The loop back test returns command messages directly as response messages without changing the contents to
check the communications between the master and slave.
The following table shows a message example for performing a loop back test with the slave no. 1.
Command Message
Slave address
Function code
Test Code
Data
CRC-16
86
6-
(During Normal Operation)
02H
Slave Address
03H
Function Code
Higher
00H
Lower
20H
1st storage
register
Higher
00H
Lower
04H
Next storage
register
Higher
45H
Lower
F0H
Next storage
register
Next storage
register
CRC-16
(During Normal Operation)
01H
Slave address
08H
Function code
Higher
00H
Test Code
Lower
00H
Higher
A5H
Data
Lower
37H
Higher
DAH
CRC-16
Lower
8DH
Response Message
02H
03H
Data quantity
08H
Higher
00H
Lower
65H
Higher
00H
Lower
00H
Higher
00H
Lower
00H
Higher
01H
Lower
F4H
Higher
AFH
Lower
82H
Response Message
01H
08H
Higher
00H
Lower
00H
Higher
A5H
Lower
37H
Higher
DAH
Lower
8DH
Response Message
(During Error)
Slave Address
02H
Function Code
83H
Error code
03H
Higher
F1H
CRC-16
Lower
31H
Response Message
(During Error)
Slave address
01H
Function code
89H
Error Code
01H
Higher
86H
CRC-16
Lower
50H