Stall Prevention: L3
Name
Para-
meter
Num-
Display
ber
Stall prevention
selection dur-
ing accel
L3-01
StallP Accel
Sel
Stall prevention
level during
accel
L3-02
StallP Accel
Lvl
5
Stall prevention
selection dur-
ing running
L3-05
StallP Run Sel
Stall prevention
level during
running
L3-06
StallP Run
Level
Reference Detection: L4
Name
Param
eter
Num-
Display
ber
Speed agreement
detection level
L4-01
Spd Agree Level
Speed agreement
detection width
L4-02
Spd Agree Width
38
5-
Description
0: Disabled (Acceleration as set.
With a too heavy load, the motor
may stall.)
1: Enabled (Acceleration stopped
when L3-02 level is exceeded.
Acceleration starts again when
the current has fallen below the
stall prevention level).
2: Intelligent acceleration mode
(Using the L3-02 level as a basis,
acceleration is automatically
adjusted. The set acceleration
time is disregarded.)
Sets the stall prevention during
acceleration operation current level
as a percentage of Inverter rated
current.
Effective when L3-01 is set to 1
or 2.
Usually changing this setting is not
necessary. Reduce the setting when
the motor stalls.
Selects the stall prevention during
running.
0: Disabled (Runs as set. With a
heavy load, the motor may stall.)
1: Deceleration using deceleration
time 1 (C1-02.)
2: Deceleration using deceleration
time 2 (C1-04.)
Set the stall prevention during run-
ning operation current level as a
percentage of the Inverter rated cur-
rent.
Effective when L3-05 is 1 or 2.
Usually changing this setting is not
necessary.
Reduce the setting when the motor
stalls.
Description
Effective when "f
/f
agree
out
set
1", "Frequency detection 1" or
"Frequency detection 2" is set
for a multi-function output.
Effective when "f
/f
agree
ref
out
1", "f
/f
agree 1" or "Fre-
out
set
quency detection 1" or "Fre-
quency detection 2" is set for a
multi-function output.
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 2
1
No
A
0 to 200
150%
No
A
0 to 2
1
No
A
30 to
150%
No
A
200
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0.0 to
A
120.0
0.0Hz
i
No
0.0 to
-
100.0
0.0 to
A
20.0
2.0Hz
i
No
0.0 to
-
40.0%
Control Methods
MEMO-
Closed
Open
Closed
BUS
Loop
Loop
Loop
Register
Vector
Vector
Vector
(PM)
A
-
-
48FH
A
-
-
490H
-
-
-
493H
-
-
-
494H
Control Methods
MEMO-
Closed
Open
Closed
BUS
Loop
Loop
Loop
Register
Vector
Vector
Vector
(PM)
A
A
-
0.0Hz
0.0Hz
499H
A
-
-
0.0%
A
A
-
2.0Hz
2.0Hz
49AH
A
-
-
4.0%
Page
6-23
6-23
6-40
6-40
Page
6-26
6-26