Connection Diagram

The connection diagram of the Inverter is shown in
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
L1
2
3-phase power
L2
380 to 480V
50/60Hz
L3
PE
Multi function
Inputs
(Factory setting)
Note:
1. Main circuit terminals are indicatied with double circles and
control circuit terminals are indicatied with a single circles
2. The CN5 factory setting is NPN
3. To enable the inverter both inputs, BB and BB1 must be closed. If
only one of the inputs is closed, "BB" will be displayed in the
operator panel and the inverter will not start.
2
2-
Magnetic
Contactor
Line
Filter
Forward run/stop
Reverse run/stop
Nominal Speed
Inspection Run
Intermediate Speed
Leveling Speed
Not used
Hardware Baseblock (note 3)
Voltage adjust-
ment
Analog input
2kOhm
(Speed reference)
0 to 10 V
2kOhm
P
Input option cards
Optional control power
to terminal B1
supply input for Rescue
to terminal -
Operation
Fig 2.1 Connection Diagram (Model CIMR-L7Z43P7 Shown Above)
Fig
2.1.
DC reactor to improve input
Braking Resistor
power factor (optional)
unit (optional)
Link
(+1)
(+2)
(-)
B1
L1(R)
L2(S)
L3(T)
S1
S2
S3
S4
PG-X2
(Optional)
S5
S6
S7
BB
BB1
+24V, 8mA
SC
IP24V (24V)
CN5(NPN setting)
E(G)
+V
Analog input power
supply +15V, 20mA
A1
Master speed
reference 0 to 10V
AC
0 V
2CN
P0
Control Power
Supply Input
N0
1
Shielded
Twisted-pair
wires
wires
1
Motor
B2
U/T1
V/T2
IM/PM
W/T3
TA1
P
P
TA3
TA2
A Pulse
Pulse Monitor Output
B Pulse
RS-422
(100m or less)
Z Pulse
2
3
MA
Fault contact output
MB
250VAC, max. 1A
MC
30VDC, max. 1A
M1
Brake Command
M2
(Factory setting)
Multi-function
M3
Contactor Control
contact output
M4
(Factory setting)
250VAC, max. 1A
30VDC, max. 1A
M5
Inverter Ready
M6
(Factory setting)
Output option
3CN
cards
2
PG