Sending Commands Using the CMND(490) Instruction

Setting CMND(490) Operands
S Operand
C Operand
90
Host
Etc.
Link
header
code
FINS header
FA
FINS
command
Remote
Etc.
MRC
SRC
unit
address
(DA2)
Any
User-
User-
except
speci-
speci-
serial
fied
fied
port
unit
address
Use the following method to send FINS commands to the Serial Communica-
tions Board/Unit from the PC.
• Set the FINS command code (2803/2804/2805 hex) in S.
• Set the data without spaces (see note) following the FINS command code
in S+1 onwards.
Note
Frames are set in the same order as in I/O memory from leftmost to rightmost
byte (without blank bytes (00 hex)).
C+2 bits 00 to 07 (Send destination network address)
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a network:
• CompoWay/F, Modbus: Depends on the system configuration.
• Host Link FINS: Always set the unit address of the serial port.
C+3 bits 08 to 15 (Remote destination node address)

• CompoWay/F, Modbus

• With routing tables that treat serial communications path as a network:
00 hex (indicates local PC communications)
• Without routing tables that treat serial communications path as a net-
work: Node address for specifying the actual remote PC
• Host Link FINS
• Host Link unit number incremented by one (1 to 32)
C+3 bits 00 to 07 (Send destination unit address)
• CompoWay/F, Modbus
Always set the unit address of the serial port
Text
FINS
End code
command
End code
FINS text
User-specified
Section 3-7
Error
check
Terminator
code
FINS text
FCS
*+CR