FINS Commands
: 04 01
5-3-13 RUN
Execution Conditions
Command Format
Response Format
Parameters
Comments

5-3-14 STOP: 04 02

188
Changes the CPU Unit's operating mode to MONITOR or RUN, enabling the
PLC to execute its program.
Note The CPU Unit will start operation when RUN is executed. You must confirm
the safety of the system before executing RUN.
When the "prohibit overwriting of protected program" setting is enabled, this
command cannot be executed.
Access right at
other device
No
RUN mode
OK
04
01
FF
Command
Program
code
No.
04
01
Command
End code
code
Program number (command)
Always FFFF (hex).
Mode (command)
Set the CPU Unit's operating mode as follows:
02 (hex):
04 (hex):
End code (response)
Refer to 5-1-3 End Codes for information on end codes.
If only the command code or only the command code and program number
are sent, the mode will be changed to MONITOR mode.
If the CPU Unit's operating mode has already been changed to the intended
mode when this command is sent, a normal completion will be returned.
Changes the CPU Unit's operating mode to PROGRAM, stopping program
execution.
Note The CPU Unit will stop operation when STOP is executed. You must confirm
the safety of the system before executing STOP.
UM read
DIP switch UM write
protection
OK
MONITOR mode
OK
FF
Mode
Change to MONITOR mode.
Change to RUN mode.
Section 5-3
Network write
protection
protection
OK
PROGRAM mode
OK
No