Parameter Area Clear: 02 03 - Omron CJ - REFERENCE MANUAL 07-2009 Reference Manual

Communications commands
Hide thumbs Also See for CJ - REFERENCE MANUAL 07-2009:
Table of Contents

Advertisement

FINS Commands
Comments
5-3-9

PARAMETER AREA CLEAR: 02 03

Execution Conditions
Command Format
Response Format
Parameters
Parameters will be written regardless of the operating mode of the CPU Unit.
There are some settings in the PLC Setup that cannot and will not be written if
the CPU Unit is in RUN mode, but the end code will be 0000 nevertheless. It is
the user's responsibility to program steps to prohibit this command from being
executed when the CPU Unit is in the RUN mode if such protection is neces-
sary. Execute CPU UNIT STATUS READ (command code 0601) to read the
CPU Unit's mode. (Refer to 5-3-17 CPU UNIT STATUS READ: 06 01.)
Data can only be written to the I/O registration table when the CPU Unit is in
PROGRAM mode.
All words in the specified parameter area must be written at the same time to
ensure complete data. A maximum of 498 words can be written with each
command. Nothing will be written if more than 498 words are specified. To
write larger parameter areas, use multiple commands and specify the begin-
ning word for each.
Except for the routing table area, each area must be read or written in its
entirety.
Writes all zeros to the specified number of consecutive parameter area words
to clear the previous data. The I/O table can be cleared only when the CPU
Unit is in PROGRAM mode.
Note Some PLC Setup parameters cannot be written in RUN or MONITOR mode.
Access right at
other device
No
RUN mode
OK
02
03
Command
Parameter
code
area code
02
03
Command
End code
code
Parameter area code (command)
Specify the parameter area to clear.
Beginning word (command)
Always 0000.
Number of words (command)
Specify the number of words to clear. (One word = 16 bits.) If the number of
write words is set to 0000, no words will be written and a normal end code will
be returned.
UM read
DIP switch UM
protection
write protection
OK
MONITOR mode
OK
00
00
00
Beginning
No. of
Data
word
words
Section 5-3
Network write
protection
No
No
PROGRAM mode
OK
00
183